COMMERCIAL
SINGLE PACKAGE ROOFTOP
GAS HEAT/ELECTRIC COOLING
UNITS
Bryant has designed the DuraPac Plus series based on
customer needs and requests to be the most efficient and reli-
able ever.

FEATURES/BENEFITS

• Efficient rooftop line for cooling using scroll compressor
technology
• Efficient rooftop line for heating using dimpled heat
exchangers
• High reliability — non-corrosive condensate pans, prepainted
cabinets and primed interior panels, and all units are fully
protected by internal safeties
• Quiet operation — isolated compressor plate. All compres-
sors mounted on independent vibration isolators. Standard,
belt-driven evaporator fan motors on all units
• Ease of maintenance achieved by self diagnostics on the
Integrated Gas Controller (IGC), standard size filters, no tool
filter access, simple compressor access, permanently lubri-
cated fan motors, optional disconnect switch, optional hinged
access panels, and optional 115-v convenience outlet
• Performance and comfort enhancing options — High-static
motors and Perfect Humidity™ dehumidification package.
BRYANT MEANS TOP QUALITY AND RELIABILITY —
Each component utilized in the DuraPac Plus series is
designed and tested for a minimum of 15 years operation
under the harshest conditions.
Every unit is thoroughly run tested at the factory in each oper-
ating mode and evacuated prior to final charging. Every coil is
leak-tested with helium particles. Automated run testing allows
accurate undisputed tests and measurements which are sec-
ond to none in the industry.
Each unit contains a factory printout indicating tested pres-
sures, amperages, dates, and inspectors, providing certifica-
tion of the unit's status at the time of manufacture.
Units are equipped with valuable safety controls designed to
monitor and protect for the life of the unit. The standard safe-
ties include:
• low-pressure/loss-of-charge switch
Unit 581B036-072
Unit 581B090-150
• high-pressure switch
• freeze-protection thermostat
• internal compressor overload
• exclusive Cycle-LOC™ circuit board that prevents compres-
sor cycling
• refrigerant filter drier
The cabinet is constructed of galvanized steel, bonderized and
coated with a prepainted baked enamel finish. The paint finish
is a non-chalking type, and is capable of exceeding Federal
Test Method Standard No. 141 (Method 6061) 500-Hour Salt
Spray Test. In addition, all cabinet interior surfaces are primed,
allowing the entire unit to have a longer life and more attractive
appearance.

EASY MAINTENANCE AND INSTALLATION

All Units are Factory Shipped in the Vertical Discharge
Configuration for fit-up to standard roof curbs. (One acces-
sory curb fits sizes 036-072; another accessory curb fits
sizes 090-150.) Contractors can order and install the roof curbs
early in the construction stage, before decisions on size
requirements have been made.
All Units Feature Heavy-Gage Roll-Formed Baserail design
with forklift slots on 3 sides of the unit and rigging holes for
easier maneuvering and installation. Stretch-wrap packaging
protects the unit during shipment and storage.
Units are Easily Converted from vertical to horizontal applica-
tions to make retrofit and add-on jobs easier. To convert from
vertical to horizontal discharge, simply relocate 2 panels. The
same basic unit can be used for a variety of applications and
can be quickly modified at the jobsite.
Standard high-performance, belt-driven, evaporator-fan motors
enable 581B036-150 units to operate in most ductwork
configurations.
Ductwork Connections are Made Easy by the logical 2 to 1
aspect ratio. On vertical discharge units, ductwork attaches
directly to the roof curb.
Model 581B
DuraPac Plus Series
Sizes 036-150
3 to 12
1
/
Tons
2
Form No. PDS 581B.36.5

Advertisement

Table of Contents
loading

Summary of Contents for Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B

  • Page 1 COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING UNITS Bryant has designed the DuraPac Plus series based on customer needs and requests to be the most efficient and reli- able ever. FEATURES/BENEFITS • Efficient rooftop line for cooling using scroll compressor technology •...
  • Page 2 FACTORY-INSTALLED OPTIONAL DISCONNECT SWITCH FACTORY-INSTALLED OPTIONAL CONVENIENCE OUTLET SINGLE PIECE TOP PANEL ON-SITE CONVERTIBILITY FROM VERTICAL TO HORIZONTAL DISCHARGE HIGH-EFFICIENCY COILS AND FIXED ORIFICE REFRIGERANT METERING DEVICE SLOPED, NON-CORROSIVE CONDENSATE DRAIN PAN FEATURES/BENEFITS (cont) REFRIGERATION SYSTEM PROTECTION PREMIUM QUALITY DIMPLED HEAT SCROLL COMPRESSORS EXCHANGERS NO TOOL...
  • Page 3: Table Of Contents

    4) filter driers, which trap moisture and debris in the refrigera- tion system. 5) Bryant’s exclusive fixed orifice metering device, which pre- cisely controls refrigerant flow, preventing slugging and floodback, while maintaining optimum unit performance by metering the circuits individually.
  • Page 4: Features/Benefits

    INDOOR AIR QUALITY (IAQ) The Quality of Building Air is Improved as the DuraPac Plus series utilizes certain key features that assist in improving indoor air quality. A sloped condensate pan eliminates possible biological growth in the rooftop unit. A face-split evaporator coil (090-150 sizes) design proves effective in removing additional moisture from the supply air.
  • Page 5: Ari Capacities

    UNIT NOMINAL STANDARD 581B TONS 1200 1450 1750 2100 3000 3000 3200 4300 LEGEND — Decibels — Energy Efficiency Ratio IPLV — Integrated Part-Load Value SEER — Seasonal Energy Efficiency Ratio *Air-Conditioning & Refrigeration Institute. †Applies only to units with capacity of 65,000 Btuh or less. **The IPLV is not applicable to single-compressor units.
  • Page 6: Options And Accessories

    ITEM Perfect Humidity™ Dehumidification Package Integrated Economizer — Durablade Integrated Economizer — EconoMi$er (gear driven) EconoMi$er with Power Exhaust (Vertical Only) Power Exhaust for EconoMi$er High-Static Motor (except 150) Hinged Access Panels 25% Manual Outdoor-Air Damper 50% Manual Outdoor-Air Damper Convenience Outlet Unit Mounted Disconnect Two-Position Damper (25% Open)
  • Page 7 UNIT MOUNTED DISCONNECT Factory-installed, internally-mounted, NEC (National Electrical Code) and UL (Underwriters’ Laboratories) approved non-fused switch provides unit power shutoff with disconnect lockout protection capability. The switch is accessible from outside the unit. CONVENIENCE OUTLET Factory-installed, internally mounted and externally accessible 115-v female receptacle.
  • Page 8 Accu- sensor III is available for Durablade economizers. BRYANT COMMERCIAL PROGRAMMABLE THERMOSTAT Designed specifically for use with Bryant commercial systems, this Bryant programmable thermostat features LED occupied/unoccupied displays and setback mode which can override continuous fan operation.
  • Page 9: Physical Data

    UNIT SIZE 581B NOMINAL CAPACITY OPERATING WEIGHT (lb) Unit With Durablade Economizer With EconoMi$er With Perfect Humidity™ Dehumidification Package Roof Curb COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Standard Unit Unit With Perfect Humidity Dehumidification Package CONDENSER FAN Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm...
  • Page 10 UNIT SIZE 581B FURNACE SECTION Rollout Switch Cutout Temp (F)† Burner Orifice Diameter (in..drill size)** Natural Gas — Std Liquid Propane — Alt†† Thermostat Heat Anticipator Setting (amps) (208/230/460/575 V) Gas Input (Btuh) First Stage/Second Stage Efficiency (Thermal) (%) Temperature Rise Range Manifold Pressure (in.
  • Page 11 UNIT SIZE 581B NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit With Durablade Economizer With EconoMi$er With Perfect Humidity™ Dehumidification Package Roof Curb* COMPRESSOR Quantity Oil (oz) (each compressor) REFRIGERANT TYPE Operating Charge (lb-oz) Standard Unit Circuit 1 Circuit 2 Unit With Perfect Humidity Dehumidification Package Circuit 1 Circuit 2...
  • Page 12 UNIT SIZE 581B FURNACE SECTION Rollout Switch Cutout Temp† Burner Orifice Diameter (in..drill size) Natural Gas Liquid Propane Accy Thermostat Heat Anticipator Setting (amps) 208/230 v and 575 Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh)Stage1/Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in.
  • Page 13: Base Unit Dimensions

    STANDARD DURABLADE ECONOMI$ER UNIT ECONOMIZER UNIT WEIGHT WEIGHT WEIGHT 581B 15.4 21.3 15.4 21.3 15.4 21.3 15.4 21.3 CONNECTION SIZES ″ ″ ″ ″ Dia [35] Field Power Supply Hole 2″ ″ ″ ″ Dia [51] Power Supply Knockout ″ ″ ″ ″ Dia [44] Charging Port Hole ″...
  • Page 14 STANDARD DURABLADE ECONOMI$ER UNIT UNIT WEIGHT ECONOMIZER WEIGHT 581B 1035 1050 CONNECTION SIZES ″ Dia [35] Field Power Supply Hole ″ Dia [64] Power Supply Knockout ″ Dia [44] Charging-Port Hole ″ Dia [22] Field Control Wiring Hole ″-14 NPT Condensate Drain ″-14 NPT Gas Conn.
  • Page 15: Accessory Dimensions

    ACCESSORY DIMENSIONS — 581B036-072 UNIT ROOF CURB SIZE “A” ACCESSORY 581B 1′-2″ [356] CRRFCURB001A00 036-072 2′-0″ [610] CRRFCURB002A00 D ALT UNIT SIZE “E” DRAIN 581B HOLE ″ [19] NPT ″ ″ 1′-9 1′-4″ ″ 036-072 [551] [406] [44.5] [12.7] NPT ″...
  • Page 16 ACCESSORY DIMENSIONS — 581B090-150 CONNECTOR PKG. ACCY. CRBTMPWR001A00 CRBTMPWR002A00 ″ ″ 2′-8 1′-10 CRBTMPWR003A00 [827] [583] CRBTMPWR004A00 D ALT “E” “F” “G” DRAIN POWER CONTROL HOLE ″ [19] NPT) ″ ″ ″ [31.7] [19] NPT [12.7] ″ ″ ″ [19] NPT [44.5] ″...
  • Page 17: Selection Procedure

    SELECTION PROCEDURE (With 581B048 Example) I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS. Given: Required Cooling Capacity (TC) ..44,600 Btuh Sensible Heat Capacity (SHC)... . 32,000 Btuh Required Heating Capacity .
  • Page 18: Performance Data

    581B036 (3 TONS) Temp (F) Air Ent Condenser (Edb) 41.9 20.4 2.19 40.7 19.9 2.46 39.3 19.5 2.75 37.7 18.8 3.06 36.0 18.3 3.41 34.2 17.6 3.78 581B048 (4 TONS) Temp (F) 1200/0.17 Air Ent Condenser (Edb) 54.0 50.7 26.1 32.7 2.81 2.80...
  • Page 19 581B060 (5 TONS) Temp (F) 1500/0.08 Air Ent Condenser (Edb) 70.8 65.4 34.1 42.7 3.53 3.49 68.9 63.2 33.5 41.8 3.98 3.94 66.8 60.6 32.8 40.7 4.48 4.43 64.3 57.7 32.0 39.6 5.03 4.96 61.5 54.8 31.0 38.4 5.61 5.55 58.7 51.6 30.0...
  • Page 20 581B090 (7 TONS) Temp (F) Air Ent Condenser (Edb) 105.5 50.6 5.15 102.5 49.7 5.86 98.9 48.5 6.65 95.3 47.3 7.51 91.0 45.9 8.43 86.2 44.1 9.38 581B102 (8 TONS) Temp (F) 2550/0.08 Air Ent Condenser (Edb) 119.5 105.7 56.5 65.7 5.92 5.84...
  • Page 21 581B120 (10 TONS) Temp (F) 3000/0.03 Air Ent Condenser (Edb) 140.3 129.4 65.6 82.2 7.35 7.21 137.7 125.3 65.0 81.2 8.29 8.13 133.8 120.7 63.9 79.6 9.33 9.16 128.7 115.4 62.3 77.6 10.46 10.28 123.2 109.1 60.4 75.1 11.66 11.47 117.5 101.8 58.5...
  • Page 22 COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION 581B036 (3 TONS) Temp (F) Air Ent Condenser (Edb) 41.3 17.5 2.19 38.6 15.2 2.46 35.9 13.0 2.74 33.8 10.9 3.05 31.8 3.40 28.7 3.78 581B048 (4 TONS) Temp (F) 1200/0.17 Air Ent Condenser (Edb) 52.9...
  • Page 23 COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont) 581B060 (5 TONS) Temp (F) 1500/0.08 Air Ent Condenser (Edb) 69.9 62.7 29.0 36.9 3.61 3.55 65.9 59.1 25.3 34.0 4.05 3.97 61.9 55.2 21.6 31.1 4.53 4.43 57.7 51.1 18.1 27.8 5.05 4.93 53.4...
  • Page 24 COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont) 581B090 (7 TONS) Temp (F) Air Ent Condenser (Edb) 98.4 44.5 5.05 94.2 39.7 5.74 89.9 34.8 6.42 84.6 30.0 7.26 79.2 25.2 8.10 72.8 20.1 9.10 581B102 (8 TONS) Temp (F) 2550/0.08 Air Ent Condenser...
  • Page 25 COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont) 581B120 (10 TONS) Temp (F) 3000/0.03 Air Ent Condenser (Edb) 134.3 122.5 60.0 76.1 7.03 6.84 127.6 115.4 51.5 68.8 7.96 7.86 120.9 108.3 43.0 61.5 8.88 8.87 112.0 99.9 36.1 54.1 10.0 10.0 103.0...
  • Page 26 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 5. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 6. Interpolation is permissible. Do not extrapolate.
  • Page 27 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 28 See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 29 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 30 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 31 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 2.01 2.34...
  • Page 32 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. EXTERNAL STATIC PRESSURE (in. wg) —...
  • Page 33 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 5. Use of a field-supplied motor may affect wire sizing. Contact your Bryant rep- resentative to verify. 6. Interpolation is permissible. Do not extrapolate.
  • Page 34 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant rep- resentative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 35 See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant rep- resentative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 36 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant rep- resentative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 37 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for addi- tional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 7. Interpolation is permissible. Do not extrapolate.
  • Page 38 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for addi- tional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. EXTERNAL STATIC PRESSURE (in. wg) 1.17...
  • Page 39 Unit warranty will not be affected. See Evaporator-Fan Motor Data tables on pages 41 and 42 for additional information. 6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. EXTERNAL STATIC PRESSURE (in. wg) —...
  • Page 40 UNIT RATING 581B (dB) 55.9 036,048 060,072 59.1 090-102 62.2 64.6 63.7 LEGEND ARI — Air Conditioning and Refrigeration Institute — Sound Levels (decibels) UNIT Durablade EconoMi$er ECONOMIZER Durablade EconoMi$er *Single phase/3 phase. NOTE: Convert bhp to watts using the following formula: watts = UNIT SIZE FIOP —...
  • Page 41 581B FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR STANDARD MOTOR Unit 581B 1090 1055 1185 1150 1460 1425 (single-phase) 060 (3-phase) 1585 1540 and 072 090,102 1085 1060 1080 1060 1260 1220 581B FAN RPM AT MOTOR PULLEY SETTING WITH HIGH-STATIC MOTOR HIGH-STATIC MOTOR Unit 581B...
  • Page 42 EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS UNIT UNIT MAXIMUM 581B PHASE CONTINUOUS BHP* Three 2.40 Three 2.40 Three 2.90 Three 2.90 090,102 Three 4.20 Three 5.25 LEGEND Bhp — Brake Horsepower Durablade Economizer Barometric Relief Damper Characteristics — 581B036-072 PERFORMANCE DATA (cont) MAXIMUM OPERATING WATTS* 2120...
  • Page 43 0.25 3 TO 6 TON STATIC PRESSURE (in. wg) 7 1/2 TO 12 1/2 TON EconoMi$er Outdoor-Air Leakage 0.25 0.20 0.15 0.10 0.05 0.00 3 TO 6 TON 7 1/2 TO 12 1/2 TON 2500 2000 1500 1000 STATIC PRESSURE (in. wg) EconoMi$er Power Exhaust Performance (581B036-072) PERFORMANCE DATA (cont)
  • Page 44 *As the height above sea level increases, there is less oxygen per cubic 42/43 47/50 foot of air. Therefore, heat input rate should be reduced at higher altitudes. †Orifices available through your local Bryant distributor. ALTITUDE DERATING FACTOR* 581B036-150 MAXIMUM HEATING VALUE ELEVATION...
  • Page 45: Electrical Data

    581B036-072 STANDARD MOTOR (Units Without Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-1-60 208/230-3-60 (3 Tons) 460-3-60 575-3-60 208/230-1-60 208/230-3-60 (4 Tons) 460-3-60 575-3-60 208/230-1-60 208/230-3-60 (5 Tons) 460-3-60 575-3-60 208/230-3-60 460-3-60 (6 Tons) 575-3-60 581B036-072 STANDARD MOTOR (Units With Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT...
  • Page 46 581B036-072 HIGH-STATIC MOTOR (Units Without Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 581B036-072 HIGH-STATIC MOTOR (Units With Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-3-60...
  • Page 47 581B090-150 STANDARD MOTOR (Units Without Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 581B090-150 STANDARD MOTOR (Units With Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-3-60...
  • Page 48 581B090-120 HIGH-STATIC MOTOR (Units Without Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 581B090-120 HIGH-STATIC MOTOR (Units With Electrical Convenience Outlet) VOLTAGE NOMINAL UNIT RANGE VOLTAGE 581B (V-Ph-Hz) 208/230-3-60 460-3-60 575-3-60 208/230-3-60...
  • Page 49: Application Data

    12. MINIMUM TEMPERATURE — Minimum temperature of air entering the dimpled heat exchanger is 50 F continuous and 45 F intermittent. 13. MOTOR DATA — Due to Bryant’s internal unit design (draw-thru over the motor), air path, and specially designed motors, the full horsepower (maximum continuous bhp)
  • Page 50 581B rooftop units which have the Perfect Humidity dehumidi- fication package option installed. • The Perfect Humidity dehumidification package is engineered and manufactured by Bryant for Bryant rooftop units. All appli- cation support, service, and warranty issues can therefore be handled through one company.
  • Page 51 APPLICATION DATA (cont) Perfect Humidity™ Dehumidification Option...
  • Page 52 APPLICATION DATA (cont)
  • Page 53 APPLICATION DATA (cont)
  • Page 54: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING Vertical Discharge LEGEND NEC — National Electrical Code Horizontal Discharge...
  • Page 55: Typical Wiring Schematic

    TYPICAL WIRING SCHEMATIC 581B036-072 Typical Wiring Schematic and Component Arrangement (208/230 V 3-Phase Unit Shown)
  • Page 56 581B036-072 Typical Wiring Schematic and Component Arrangement — Adjustable Heat Anticipator — Contactor, Compressor — Capacitor — Cooling Compensator — Compressor Lockout COMP — Compressor Motor — Diode — Enthalpy Control ECON — Economizer — Emergency Power Supply EQUIP — Equipment —...
  • Page 57 TYPICAL WIRING SCHEMATIC (cont) 581B090-150 Typical Wiring Schematic LEGEND — Adjustable Heat Anticipator — Burner Relay — Contactor, Compressor — Capacitor — Circuit Breaker — Cooling Compensator — Compressor Lockout COMP — Compressor Motor CONN — Connection — Control Relay —...
  • Page 58: Controls

    OPERATING SEQUENCE FOR 581B036-072 UNITS Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 and the compressor contactor (C) are energized. The indoor (evaporator) fan motor (IFM), compressor, and outdoor (condenser) fan motor (OFM) start. The OFM runs continuously while the unit is in cooling.
  • Page 59 If the supply-air temperature falls below 52 F, a switch on the supply-air thermostat is closed between the T1 terminal and the 24 vac terminal. This causes the damper to modulate closed until the supply-air temperature rises above 55 F or the damper reaches the minimum position.
  • Page 60: Guide Specifications

    SIZE RANGE: 3 TO 12 TONS, NOMINAL COOLING 72,000 TO 250,000 BTUH, NOMINAL INPUT HEATING BRYANT MODEL NUMBER: 581B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop- or slab-mounted, electrically controlled heating and cooling utilizing a scroll compressor for cool- ing duty and gas combustion for heating duty.
  • Page 61 I. Controls and Safeties: 1. Unit Controls: Unit shall be complete with self-contained low- voltage control circuit protected by a fuse on the 24-v transformer side. 2. Safeties: a. Unit shall incorporate a solid-state compressor protector which provides anti-cycle reset capabil- ity at the space thermostat, should any of the following standard safety devices trip and shut off compressor.
  • Page 62 11. Return-Air Temperature Sensor: The return-air temperature sensor shall be used with the EconoMi$er device. When used in conjunction with outdoor-air temperature EconoMi$er device will provide differential tempera- ture control. 12. Indoor-Air Quality (CO ) Sensor: Shall have the ability to provide demand ventilation indoor-air quality (IAQ)
  • Page 64 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Copyright 2000 Bryant Heating & Cooling Systems Printed in U.S.A. 12/00 Catalog No. 5258-103...