Electrical Data - Bryant 579F User Manual

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

UNIT SIZE
NOMINAL
IFM TYPE
581B
V-PH-Hz
STD
208/230-3-60
HIGH
STD
460-3-60
102
HIGH
(8
1
/
Tons)
2
STD
575-3-60
HIGH
PH
STD
208/230-3-60
HIGH
STD
460-3-60
120
HIGH
(10 Tons)
STD
575-3-60
HIGH
PH
208/230-3-60
STD
460-3-60
STD
150
(12
1
/
Tons)
2
ST
575-3-60
PH
LEGEND
CONV
— Convenience Outlet
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
PH
— Perfect Humidity™ Dehumidification System
RLA
— Rated Load Amps
UL
— Underwriters' Laboratories
*The values listed in this table do not include power exhaust. See table at right for power
exhaust requirements.
†Used to determine minimum disconnect per NEC.
**Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
ELECTRICAL DATA (cont)
581B036-150 UNITS
VOLTAGE
COMPRESSOR (each)
CONV
RANGE
OUTLET
Min
Max
Qty
NO
YES
187
254
2
NO
YES
NO
YES
414
508
2
NO
YES
NO
YES
NO
518
632
2
YES
NO
YES
NO
YES
187
254
2
NO
YES
NO
YES
414
508
2
NO
YES
NO
YES
NO
518
632
2
YES
NO
YES
NO
187
254
2
YES
NO
414
508
2
YES
NO
YES
518
632
2
NO
YES
452 + 464 + 455
=
3
1371
=
3
= 457
OFM (each)
IFM
FLA
RLA
LRA
Qty
FLA
7.5
13.1
105
2
1.4
10.6
3.4
7.4
55
2
0.7
4.8
2.8
0.6
6.4
44
2
3.3
0.7
4.8
10.6
17.6
125
2
1.4
15.0
4.8
8.3
62.5
2
0.7
7.4
3.3
2
0.6
6.3
50
5.6
2
0.7
7.4
19
156
2
1.4
15.0
9
75
2
0.7
7.4
2
0.6
5.6
7.4
54
2
0.7
7.4
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
N/A — Not Available
*Single or three phase.
NOTE: If a single power source is to be used, size wire to include power exhaust MCA
and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the
new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change.
The MOCP in this example is 35 amps and the MCA New is below 35; therefore the
MOCP is acceptable. If "MCA New" is larger than the published MOCP, raise the MOCP
to the next larger size. For separate power, the MOCP for the power exhaust will be
15 amps per NEC.
138
COMBUSTION
POWER SUPPLY*
FAN MOTOR
FLA
MCA
MOCP**
40.2
45
46.2
50
0.6
43.3
50
49.3
60
21.5
25
24.2
30
0.3
22.9
25
25.6
30
18.2
20
20.4
25
0.3
18.9
25
21.1
25
19.4
25
0.3
21.5
25
53.0
60
0.6
59.0
70
57.4
70
0.6
63.4
70
24.9
30
27.6
30
0.3
27.5
30
30.2
35
19.1
25
0.3
21.3
25
21.0
25
0.3
23.1
25
21.2
25
0.3
23.4
25
60.6
70
0.6
66.6
70
29.1
35
0.3
31.8
35
23.5
30
0.3
25.6
30
23.7
30
0.3
25.9
30
7
457
= 1.53%
APPLICATION
MCA
MCA
USAGE
(230 V)
(460 V)
(575 V)
036-072*
1.6
N/A
036-072
N/A
0.68
090-150*
3.4
N/A
090-150
N/A
1.4
ALL*
1.7
N/A
ALL
N/A
0.7
MINIMUM UNIT
DISCONNECT SIZE†
FLA
LRA
42
276
48
281
46
301
51
305
23
143
25
145
24
156
27
158
19
115
21
116
20
124
22
126
20
124
22
126
56
341
61
345
61
364
66
369
26
171
29
173
29
182
32
184
20
136
22
138
23
146
25
148
23
146
25
148
64
426
70
431
31
207
33
209
25
154
27
156
25
154
27
156
MOCP
MCA
(separate
power source
only)
0.64
15
N/A
15
1.32
15
N/A
15
0.68
15
N/A
15

Hide quick links: