ELECTRICAL DATA — 581A210-300 WITH OPTIONAL CONVENIENCE OUTLET
VOLTAGE
NOMINAL
RANGE
UNIT
VOLTAGE
No. 1
581A
(3 Ph,
Min
Max
RLA
60 Hz)
208/230
187
253
16.7
210
460
414
506
9
575
518
633
7
208/230
187
253
22.4
240
460
414
506
10.7
575
518
633
9.3
208/230
187
253
47.1
300
460
414
506
19.6
575
518
633
15.8
FLA
Full Load Amps
HACR —
Heating, Air Conditioning and
Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
ELECTRICAL DATA — 581A (cont)
COMPRESSOR
No. 2
No. 3
LRA
RLA
LRA
RLA
LRA
Qty
130
16.7
130
22.4
184
4
70
9
70
10.7
90
4
55
7
55
9.3
73
4
184
22.4
184
22.4
184
4
90
10.7
90
10.7
90
4
73
9.3
73
9.3
73
4
245
47.1
245
6
125
19.6
125
6
100
15.8
100
-
-
6
LEGEND
MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
average voltage
POWER
OFM
IFM
EXHAUST
FLA
Hp
Hp
FLA
Qty Hp
(ea)
3.7
10.6/ 9.6
2
0.25
1.5
5
16.7/15.2
2
7.5
24.2/22
2
3.7
4.8
2
0.25
0.7
5
7.6
2
7.5
11
2
3
3.9
2
0.25
0.7
5
6.1
2
7.5
9
2
3.7
10.6/ 9.6
2
5
16.7/15.2
2
0.25
1.5
7.5
24.2/22
2
10
30.8/28
2
3.7
4.8
2
5
7.6
2
0.25
0.7
7.5
11
2
10
14
2
5
6.1
2
0.25
0.7
7.5
9
2
10
11
2
5
16.7/15.2
2
0.25
1.5
7.5
24.2/22
2
10
30.8/28
2
5
7.6
2
0.25
0.7
7.5
11
2
10
14
2
5
6.1
2
0.25
0.7
7.5
9
2
10
11
2
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.
:
IMPORTANT
If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.
277
COMBUSTION
POWER SUPPLY
FAN MOTOR
FLA
FLA
MCA
(ea)
83/ 82
1
5.9
95/ 94
89/ 88
0.5
1
5.9
101/ 99
97/ 94
1
5.9
109/106
42
1
3.1
48
45
0.3
1
3.1
51
48
1
3.1
54
35
1
2.4
40
38
0.24
1
2.4
42
40
1
2.4
45
94/ 93
1
5.9
106/105
101/ 99
1
5.9
112/111
0.5
108/106
1
5.9
120/118
117/113
1
5.9
129/125
45
1
3.1
52
48
1
3.1
54
0.3
52
1
3.1
58
55
1
3.1
62
42
1
2.4
47
45
0.24
1
2.4
50
47
1
2.4
52
137/135
1
5.9
148/147
144/142
0.5
1
5.9
156/154
151/148
1
5.9
163/160
59
1
3.1
65
62
0.3
1
3.1
69
65
1
3.1
72
49
1
2.4
54
52
0.24
1
2.4
57
54
1
2.4
59
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
=
457
7
457
= 1.53%
DISCONNECT
SIZE
MOCP*
FLA
100/100
89/ 88
100/100
103/101
100/100
96/ 94
110/100
110/108
100/100
105/102
125/125
118/116
50
45
50
52
50
48
60
56
50
52
60
59
40
38
45
43
45
40
50
46
45
44
50
49
100/100
102/101
125/125
116/115
110/100
109/107
125/125
123/121
125/125
118/115
125/125
131/129
125/125
125/122
150/150
139/136
50
49
60
56
50
52
60
59
60
56
60
63
60
60
70
67
50
46
50
51
50
49
50
55
50
51
60
57
175/175
144/142
175/175
157/155
175/175
152/150
200/200
166/163
175/175
160/157
200/200
173/170
60
62
80
69
80
66
80
73
80
69
90
77
60
52
60
57
60
55
60
60
60
57
60
63