581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C OFF
Temp (F)
5400/0.03
Air Entering
Condenser
(Edb)
50
55
TC
90
93
65
SHC
38
35
kW
8.8
8.8
TC
68
71
75
SHC
24
21
kW
9.6
9.6
TC
47
49
85
SHC
11
7
kW
10.3
10.3
TC
25
27
95
SHC
–2
–8
kW
11.1
11.1
581A210 (18 TONS) UNIT WITH HOT GAS REHEAT — A AND B IN REHEAT, C ON
Temp (F)
5400/0.03
Air Entering
Condenser
(Edb)
50
55
TC
147
155
65
SHC
81
76
kW
11.9
12.0
TC
128
136
75
SHC
67
61
kW
13.2
13.2
TC
108
117
85
SHC
54
46
kW
14.5
14.5
TC
89
98
95
SHC
40
31
kW
15.8
15.7
581A240 (20 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE
Temp (F)
6000/0.04
Air Entering
Condenser
(Edb)
57
62
67
TC
216
234
255
75
SHC
213
199
171
kW
13.9
14.2
14.6
TC
211
227
249
85
SHC
209
194
168
kW
15.4
15.8
16.2
TC
207
220
240
95
SHC
205
192
164
kW
17.2
17.5
17.9
TC
201
214
232
105
SHC
197
190
161
kW
19.0
19.3
19.8
TC
195
206
224
115
SHC
191
185
158
kW
21.0
21.3
21.8
TC
189
198
215
125
SHC
184
179
154
kW
23.1
23.4
24.0
LEGEND
BF
— Bypass Factor
Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW
— Compressor Motor Power Input
ldb
— Leaving Dry-Bulb
lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
= t
ldb
edb
1.10 x cfm
t
= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
lwb
rator coil (h
)
lwb
total capacity (Btuh)
h
= h
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
PERFORMANCE DATA (cont)
COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont)
6300/0.04
60
50
55
95
91
94
33
40
37
8.8
8.8
8.8
73
69
72
18
26
23
9.6
9.6
9.6
51
47
50
3
13
9
10.3
10.3
10.3
29
26
27
–12
0
–5
11.1
11.1
11.1
6300/0.04
60
50
55
162
148
157
72
84
79
12.0
11.9
12.0
143
129
137
56
70
63
13.2
13.2
13.2
124
109
118
39
56
48
14.5
14.5
14.5
105
89
98
23
42
33
15.7
15.8
15.7
7000/0.05
72
57
62
67
279
226
243
265
141
225
217
185
15.0
14.0
14.4
14.8
15.3
272
221
237
258
141
221
214
182
16.7
15.7
16.0
16.4
16.9
262
217
228
250
134
217
209
179
18.4
17.4
17.7
18.2
18.6
253
211
221
238
131
211
206
172
20.3
19.3
19.5
20.0
20.6
245
205
213
230
129
205
201
171
22.4
21.3
21.5
22.0
22.7
235
198
204
221
125
198
194
167
24.7
23.5
23.7
24.2
24.8
Evaporator Air Quantity — Cfm/BF
7200/0.05
Evaporator Air — Relative Humidity (%)
60
50
55
60
97
92
95
98
35
41
39
37
8.8
8.8
8.8
8.8
74
70
73
75
20
28
25
22
9.6
9.6
9.6
9.6
52
48
50
52
5
15
11
7
10.3
10.3
10.3
10.3
29
26
28
29
–10
2
–-3
–8
11.1
11.1
11.1
11.1
Evaporator Air Quantity — Cfm/BF
7200/0.05
Evaporator Air — Relative Humidity (%)
60
50
55
60
164
150
158
165
75
86
81
77
12.0
11.9
12.0
12.0
144
130
138
146
58
72
65
60
13.2
13.2
13.2
13.2
125
110
118
126
41
58
50
43
14.5
14.5
14.5
14.5
106
89
98
106
25
44
34
26
15.7
15.8
15.7
15.7
Air Entering Evaporator — Cfm/BF
8000/0.06
Air Entering Evaporator — Ewb (F)
72
57
62
67
72
290
237
251
273
298
151
237
232
198
159
14.3
14.5
15.0
15.4
282
232
243
265
287
148
232
228
195
155
15.9
16.1
16.6
17.1
269
228
235
254
278
142
228
222
190
152
17.7
17.9
18.3
18.8
261
221
228
247
266
140
221
216
188
146
19.5
19.7
20.2
20.7
252
214
219
236
258
137
214
209
183
145
21.6
21.7
22.2
22.8
239
207
210
225
244
132
207
201
179
139
23.8
23.9
24.4
25.0
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
FACTOR
(BF)
.05
.10
.20
.30
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
246
8100/0.06
50
55
60
50
93
96
99
94
43
40
38
44
8.8
8.8
8.8
8.8
71
74
76
72
30
26
23
31
9.6
9.6
9.6
9.6
49
51
53
49
17
12
9
18
10.3
10.3
10.3
10.3
26
28
30
27
3
–2
–6
5
11.1
11.1
11.1
11.1
8100/0.06
50
55
60
50
151
160
167
152
88
83
79
90
11.9
12.0
12.0
11.9
131
139
147
132
74
67
62
76
13.2
13.2
13.2
13.2
110
119
127
111
60
52
45
61
14.5
14.5
14.5
14.5
90
99
107
90
45
36
28
47
15.8
15.7
15.7
15.8
9000/0.07
57
62
67
72
57
247
256
279
305
256
247
241
211
168
256
14.5
14.6
15.1
15.6
14.6
242
250
270
293
250
242
237
206
163
250
16.1
16.3
16.7
17.2
16.3
236
241
259
286
243
236
230
202
161
243
17.9
18.0
18.4
19.0
18.1
229
234
251
271
236
229
223
200
155
236
19.8
19.9
20.3
20.8
20.0
221
225
240
262
228
221
215
194
152
228
21.8
21.9
22.3
22.9
22.0
214
216
229
248
220
214
207
191
147
220
24.0
24.1
24.5
25.1
24.2
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
81
82
83
84
85
Correction Factor
1.04
2.07
3.11
4.14
5.18
.98
1.96
2.94
3.92
4.90
.87
1.74
2.62
3.49
4.36
.76
1.53
2.29
3.05
3.82
9000/0.07
55
60
97
100
42
40
8.8
8.8
74
77
28
25
9.6
9.6
51
53
14
10
10.3
10.3
29
30
0
–5
11.1
11.1
9000/0.07
55
60
161
168
85
80
12.0
12.0
140
148
69
63
13.2
13.2
120
127
53
46
14.5
14.5
99
107
37
29
15.7
15.7
10,000/0.08
62
67
72
263
284
310
251
223
176
14.8
15.2
15.7
255
275
300
244
220
173
16.4
16.8
17.4
247
264
290
236
214
169
18.2
18.6
19.1
239
255
278
229
212
165
20.0
20.4
21.0
231
243
265
221
207
160
22.1
22.4
23.0
222
232
251
212
202
154
24.3
24.6
25.2
under 75
over 85
Use formula
shown below.