Electrical Data - Bryant 579F User Manual

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
581A
(3 Ph, 60 Hz)
Min
208/230
187
155
(Standard
460
414
IFM)
575
518
208/230
187
155
(Optional
IFM)
460
414
208/230
187
180
460
414
575
518
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of volt-
age imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
ELECTRICAL DATA — 581A (cont)
ELECTRICAL DATA — 581A155,180
COMPRESSOR
No. 1
No. 2
Max
RLA
LRA
RLA
LRA
Qty
253
20.7
156
20.7
156
506
10.0
75
10.0
75
633
8.2
54
8.2
54
253
20.7
156
20.7
156
506
10.0
75
10.0
75
253
32.1
195
20.7
156
506
16.4
95
10.0
75
633
12.0
80
8.2
54
OFM
IFM
Hp
FLA (ea)
Hp
FLA
3
0.5
1.70
2.9
8.8/ 8.4
3
0.5
0.80
2.9
4.2
3
0.5
0.75
3.0
3.9
3
0.5
1.70
3.7
10.5/11.0
3
0.5
0.80
3.7
4.8
3
0.5
1.70
5.0
15.8/15.8
3
0.5
0.80
5.0
7.9
3
0.5
0.75
5.0
6.0
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
275
POWER
COMBUSTION
EXHAUST
FAN MOTOR
FLA
LRA
FLA
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
4.6
18.8
0.57
0.30
2.3
6.0
0.30
0.57
2.1
4.8
0.57
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
7
457
= 1.53%
POWER
SUPPLY
MCA
MOCP*
60/60
80/80
65/65
80/80
29
35
31
40
25
30
27
30
62/63
80/80
67/67
80/80
30
35
32
40
82/82
110/110
86/86
110/110
41
50
43
50
31
40
34
45