Bryant 579F User Manual page 165

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

UNIT
581C
024-048
LEGEND
ARI — Air Conditioning and Refrigeration Institute
NOTE: Indoor sound power is available in Bryant's Electronic Catalog Program (ECAT) for
specific operating parameters.
UNIT
NOMINAL
IFM TYPE
SIZE
V-PH-Hz
024
208/
STD
230-1-60
(2 tons)
208/
STD
230-1-60
STD
208/
230-3-60
HS
STD
036
460-3-60
(3 tons)
HS
STD
575-3-60
HS
Perfect Humidity
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters' Laboratories
*The values listed in this table do not include power exhaust. See table at right
for power exhaust requirements.
**Fuse or HACR circuit breaker.
†460v motor
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature ± 10%
voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of volt-
age
imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
ARI
A-WEIGHTED
RATING
(db)
(decibels)
76
76.0
060
80
80.0
PERFORMANCE DATA — 581C
VOLTAGE
RANGE
COMPRESSOR
Min
Max
QTY
RLA
187
254
1
10.9
187
254
1
16
187
254
1
10.3
414
508
1
5.1
518
632
1
4.2
452 + 464 + 455
3
1371
=
3
= 457
SOUND DATA
OCTAVE BANDS
63
125
250
500 1000 2000 4000 8000
55.9 66.0 64.0 66.2 68.4
59.1 68.9 68.7 71.9 74.0
581C024-036
COMBUSTION
OFM
FAN MOTOR
LRA
QTY
FLA
FLA
63
1
0.7
0.6
88
1
0.7
0.6
77
1
0.7
0.6
39
1
0.4
0.3
1
0.4
31
0.3†
1
0.4†
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH028A01
CRPWREXH029A01
* — Single or three phase rooftop unit
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following
formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B060—unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would
not change. The MOCP in this example is 35 amps and the MCA New is
below 35; therefore the MOCP is acceptable. If "MCA New" is larger than
the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.
165
64.5
61.7
57.3
68.9
65.7
59.0
POWER SUPPLY
CONV
IFM
*
OUTLET
MOCP
MCA
FLA
**
NO
16.3
20
2.0
YES
22.3
25
NO
25.6
30
4.9
YES
31.6
35
NO
18.5
25
4.9
YES
24.5
30
NO
19.4
25
5.8
YES
25.4
30
NO
9.0
15
2.2
YES
11.7
15
NO
9.4
15
2.6
YES
12.1
15
NO
7.6
10
1.9
YES
9.7
15
NO
7.7
10
2.0
YES
9.8
15
NO
7.7
10
2.6†
YES
9.8
15
7
457
= 1.53%
Application
MCA
MCA
usage
(230 v)
(460 v)
036-072
1.6
N/A
036-072
N/A
0.68
ALL*
1.7
N/A
ALL
N/A
0.7
MINIMUM UNIT
DISCONNECT
SIZE
FLA
LRA
15.6
69
21.2
73
24.8
101
30.4
106
18.3
90
23.8
95
19.3
120
24.9
124
8.9
46
11.4
48
9.3
60
11.8
63
7.5
36
9.5
38
7.6
43
9.6
44
8.0
48
9.6
50
MOCP
(for
MCA
separate
(575 v)
power
source)
0.64
15
N/A
15
0.68
15
N/A
15