Bryant 579F User Manual page 186

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

579F216 (18 Tons) (cont)
Temp (F)
Air Entering
Condenser
(Edb)
54/0.65
TC
223
75
SHC
223
kW
14.3
TC
216
85
SHC
216
kW
15.8
TC
210
95
SHC
210
kW
17.6
TC
202
105
SHC
202
kW
19.4
TC
195
115
SHC
195
kW
21.3
TC
193
117
SHC
193
kW
21.7
TC
191
120
SHC
191
kW
22.3
LEGEND
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
Compressor Motor Power Input
ldb
Leaving Dry-Bulb
lwb
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t
=
t
ldb
edb
1.10 x cfm
Wet-bulb temperature corresponding to enthalpy of air
t
=
lwb
leaving evaporator coil (h
total capacity (Btuh)
h
= h
lwb
ewb
4.5 x cfm
Where: h
= Enthalpy of air entering evaporator coil
ewb
PERFORMANCE DATA — 579F (cont)
COOLING CAPACITIES (cont)
58/0.53
62/0.40
223
223
14.3
217
217
15.9
210
210
17.6
202
202
19.4
195
195
21.3
193
193
21.7
191
191
22.3
)
lwb
Evaporator Air Quantity — Cfm
9000
Evaporator Air — Ewb (F)/BF
67/0.25
228
239
202
181
14.4
14.6
222
231
194
177
16.0
16.3
215
223
187
174
17.7
18.0
207
214
184
170
19.5
19.7
196
204
192
166
21.4
21.7
194
202
192
166
21.7
22.0
191
199
191
164
22.3
22.6
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
BYPASS
FACTOR
(BF)
0.05
1.04
0.10
0.98
0.20
0.87
0.30
0.76
0.40
0.65
0.50
0.55
0.60
0.44
0.70
0.33
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
186
72/0.23
76/0.23
258
275
144
113
15.0
15.4
250
266
141
110
16.7
17.1
241
257
138
107
18.4
18.8
231
134
20.2
221
131
22.2
219
130
22.6
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
81
82
83
84
85
Correction Factor
2.07
3.11
4.14
5.18
1.96
2.94
3.92
4.91
1.74
2.62
3.49
4.36
1.53
2.29
3.05
3.82
1.31
1.96
2.62
3.27
1.09
1.64
2.18
2.73
0.87
1.31
1.74
2.18
0.65
0.98
1.31
1.64
80/0.05
under 75
over 85
Use formula
shown below.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

581a581b581c580f