Bryant 579F User Manual page 242

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

581A240 (20 Tons)
Temp (F)
Air Ent
Cond
54
58
62
TC
235
242
248
60
SHC
235
224
212
kW
11.5
11.6
11.7
TC
231
237
242
SHC
231
220
209
70
kW
13.1
13.2
13.3
TC
228
234
239
SHC
228
218
208
75
kW
13.9
14
14.1
TC
223
227
231
SHC
223
213
204
85
kW
15.6
15.7
15.8
TC
216
219
223
SHC
216
208
200
95
kW
17.4
17.5
17.6
TC
208
211
214
SHC
208
202
195
105
kW
19.3
19.4
19.5
TC
200
202
204
SHC
200
195
190
115
kW
21.3
21.4
21.5
TC
191
192
193
SHC
191
188
185
125
kW
23.5
23.5
23.6
581A240 (20 Tons) (cont)
Temp (F)
Air Ent
Cond
54
58
TC
265
266
60
SHC
265
262
kW
12
12
TC
260
261
70
SHC
260
258
kW
13.6
13.6
TC
256
257
75
SHC
256
255
kW
14.5
14.5
TC
250
250
85
SHC
250
250
kW
16.2
16.2
TC
242
242
95
SHC
242
242
kW
18.1
18.1
TC
233
233
105
SHC
233
233
kW
20.1
20.1
TC
223
223
115
SHC
223
223
kW
22.2
22.1
TC
213
212
125
SHC
213
212
kW
24.3
24.3
LEGEND
BF
— Bypass Factor
Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW
— Compressor Motor Power Input
ldb
— Leaving Dry-Bulb
lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
sensible capacity (Btuh)
t ldb = t edb –
1.10 x cfm
t lwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (h lwb )
total capacity (Btuh)
h lwb = h ewb –
4.5 x cfm
Where: h ewb = Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
PERFORMANCE DATA (cont)
COOLING CAPACITIES — STANDARD UNITS (cont)
6,000/0.04
67
72
76
80
54
267
288
306
323
247
178
143
115
86.6
247
12
12.4
12.7
13
11.7
261
282
300
316
242
175
141
113
84.5
242
13.6
14
14.3
14.6
13.3
257
278
295
311
239
174
139
112
83.1
239
14.5
14.9
15.2
15.6
14.1
250
270
287
303
234
171
136
109
80.5
234
16.2
16.6
17.1
17.4
15.8
241
260
277
292
226
167
132
105
77.2
226
18.1
18.6
19
19.4
17.7
231
249
265
279
218
163
129
101
73.6
218
20
20.6
21
21.5
19.6
220
237
253
266
209
158
124
97.2
69.5
209
22
22.7
23.2
23.6
21.7
208
224
239
251
199
153
120
92.8
65.3
199
24.2
24.8
25.4
25.9
23.8
9,000/0.06
62
67
72
267
284
305
260
216
166
12
12.3
12.7
261
277
298
256
213
164
13.6
13.9
14.3
258
273
294
254
211
162
14.5
14.8
15.2
250
265
285
249
208
159
16.2
16.5
17
242
255
274
242
204
155
18.1
18.4
18.9
233
244
263
233
200
152
20.1
20.4
21
223
232
250
223
195
147
22.1
22.5
23.1
212
219
234
212
189
142
24.3
24.6
25.2
Evap Air — Cfm/BF
7,000/0.05
Evap Air — Ewb (F)
58
62
67
72
76
251
256
274
296
312
238
230
191
151
119
11.8
11.8
12.1
12.5
12.8
246
250
268
289
305
234
227
189
149
117
13.3
13.4
13.7
14.1
14.4
243
246
264
285
301
232
225
187
147
115
14.2
14.2
14.6
15
15.3
236
238
256
277
292
227
221
184
144
112
15.9
15.9
16.3
16.8
17.2
228
230
247
267
282
221
217
180
141
109
17.7
17.8
18.2
18.7
19.1
219
220
236
256
270
215
212
176
137
105
19.6
19.7
20.2
20.8
21.2
210
210
225
243
257
207
206
171
132
101
21.7
21.7
22.2
22.9
23.3
199
200
212
230
243
199
199
166
128
96.4
23.8
23.8
24.4
25
25.5
Evap Air — Cfm/BF
Evap Air — Ewb (F)
76
80
54
58
321
338
272
272
126
87
272
271
12.9
13.2
12.1
12.1
315
331
266
267
124
85
266
267
14.6
14.9
13.7
13.7
310
326
263
263
123
83.7
263
263
15.5
15.8
14.6
14.6
301
316
257
256
120
81
257
256
17.4
17.7
16.4
16.4
288
304
248
248
116
77.8
248
248
19.3
19.7
18.3
18.3
275
291
239
239
112
74.2
239
239
21.4
21.8
20.3
20.2
262
276
229
228
108
70.2
229
228
23.5
24
22.3
22.3
247
258
218
217
103
65.4
218
217
25.7
26.2
24.5
24.5
BYPASS
FACTOR
(BF)
.05
.10
.20
.30
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4. Use chart below for bypass factor.
CFM
54
6,000
0.386
7,000
0.444
8,000
0.492
9,000
0.532
10,000
0.566
242
8,000/0.05
80
54
58
62
67
330
257
259
262
279
87
257
251
246
204
13.1
11.9
11.9
11.9
12.2
323
252
254
256
273
84.9
252
247
243
201
14.8
13.4
13.5
13.5
13.8
318
249
250
252
269
83.6
249
245
241
199
15.7
14.3
14.3
14.4
14.7
310
243
244
245
261
80.9
243
240
236
196
17.6
16
16.1
16.1
16.5
298
235
235
236
251
77.7
235
233
231
192
19.6
17.9
17.9
17.9
18.3
285
226
226
226
241
74
226
226
225
188
21.6
19.9
19.9
19.9
20.3
271
217
217
217
229
70
217
217
217
183
23.8
21.9
21.9
21.9
22.4
255
207
207
206
216
65.7
207
207
206
178
26
24.1
24.1
24.1
24.5
10,000/0.07
62
67
72
272
287
307
271
227
173
12.1
12.4
12.7
267
281
301
267
225
171
13.7
14
14.3
263
277
296
263
223
169
14.6
14.9
15.2
256
268
287
256
220
166
16.4
16.6
17
248
258
276
248
215
162
18.2
18.5
19
239
247
264
239
211
158
20.2
20.5
21
228
235
251
228
206
154
22.3
22.6
23.1
217
222
235
217
200
148
24.5
24.7
25.3
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
81
82
83
84
85
Correction Factor
1.04
2.07
3.11
4.14
5.18
.98
1.96
2.94
3.92
4.90
.87
1.74
2.62
3.49
4.36
.76
1.53
2.29
3.05
3.82
ENTERING WET-BULB (F)
58
62
67
72
Bypass Factor
0.197
0.108
0.109
0.134
0.260
0.131
0.121
0.138
0.321
0.163
0.133
0.145
0.375
0.205
0.146
0.154
0.420
0.245
0.158
0.164
72
76
80
300
317
333
159
123
86.7
12.6
12.9
13.1
293
310
326
156
120
84.6
14.2
14.5
14.8
290
305
322
155
119
83.5
15.1
15.4
15.8
282
296
314
152
116
81.3
16.9
17.3
17.7
272
285
303
148
112
78
18.9
19.2
19.7
260
273
290
145
108
74.4
20.9
21.3
21.8
248
260
275
140
104
70.4
23
23.4
23.9
232
245
257
135
99.8
65.5
25.1
25.7
26.1
76
80
325
340
130
86.7
13
13.3
317
333
127
84.7
14.6
15
312
327
126
83.4
15.6
15.9
303
317
123
80.7
17.4
17.7
292
306
120
77.6
19.4
19.7
279
291
116
73.9
21.5
21.8
263
276
111
69.9
23.6
24
248
259
106
65.2
25.8
26.2
under 75
over 85
Use formula
shown below.
76
80
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000