580F300275 (25 TONS)*
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
7,000
941
3.35
7,500
999
4.05
8,000
1058
4.85
8,500
1117
5.74
9,000
1177
6.75
9,500
1237
7.98
10,000
1297
9.12
10,500
1358
10.49
11,000
1418
12.00
11,250
1449
12.80 10,585
580F300275 (25 TONS)* (cont)
Available External Static Pressure (in. wg)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
7,000
1274
6.35
5248
7,500
1316
7.20
6960
8,000
1360
8.14
6734
8,500
1406
9.20
7605
9,000
1453
10.36
8568
9,500
1501
11.64
9627
10,000
10,500
11,000
11,250
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-
static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
580F300360 (25 TONS)*
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
7,000
992
4.05
7,500
1055
4.77
8,000
1118
5.58
8,500
1182
6.46
9,000
1246
7.42
9,500
1310
8.47
10,000
1374
9.61
10,500
1439
10.84
11,000
1503
12.17 10,059
11,250
1536
12.86 10,636
580F300360 (25 TONS)* (cont)
Available External Static Pressure (in. wg)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
7,000
1311
6.51
5385
7,500
1358
7.30
6039
8,000
1406
8.17
6767
8,500
1456
9.12
7541
9,000
1507
10.15
8393
9,500
10,000
10,500
11,000
11,250
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-
static drive range is 1332 to 1550. Other rpms require a field-supplied drive.
1. Static pressure losses (i.e., EconoMi$er IV) must be added to external static
pressure before entering Fan Performance table.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing losses. See
Accessory/FIOP Static Pressure table on page 223.
PERFORMANCE DATA (cont)\
FAN PERFORMANCE — 580F180-300 UNITS (cont)
Available External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
2,769
1002
3.80
3,140
1061
3,348
1057
4.53
3,742
1112
4,007
1113
5.35
4,424
1165
4,750
1169
6.28
5,190
1219
5,583
1226
7.31
6,047
1274
6,511
1284
8.46
6,999
1329
7,450
1342
9.74
8,051
1385
8,674
1400
11.14
9,209
1442
9,919
1459
12.67 10,478
1.6
Rpm
Bhp
Watts
Rpm
1323
6.92
5,718
1371
1364
7.79
6,437
1410
1406
8.76
7,239
1450
1449
9.83
8,129
1492
1495
11.02
9,111
1536
1541
12.32 10,190
Available External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
3,348
1051
4.44
3,668
1106
3,947
1110
5.17
4,277
1162
4,610
1170
5.99
4,950
1220
5,339
1231
6.88
5,690
1278
6,136
1292
7.86
6,498
1337
7,005
1354
8.92
7,377
1397
7,947
1416
10.07
8,329
1457
8,964
1479
11.32
9,356
1518
1542
12.65 10,460
1.6
Rpm
Bhp
Watts
Rpm
1359
6.96
5751
1405
1403
7.76
6412
1448
1560
8.63
7137
1492
1498
9.59
7929
1539
1548
10.63
8790
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
0.6
0.8
Bhp
Watts
Rpm
Bhp
Watts
4.27
3528
1117
4.76
3,934
5.02
4152
1166
5.54
4,579
5.87
4856
1216
6.41
5,304
6.83
5645
1268
7.40
6,114
7.89
6524
1320
8.48
7,015
9.07
7499
1374
9.69
8,012
10.37
8574
1428
11.02
9,110
11.80
9755
1483
12.47 10,314
1.8
Bhp
Watts
5.54
6204
6.41
6939
7.40
7759
8.48
8666
9.69
9667
Refer to this page for general Fan Performance Data notes.
NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v)
and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm. See Evaporator Fan Motor Perfor-
mance table for more information.
0.6
0.8
Bhp
Watts
Rpm
Bhp
Watts
4.83
3995
1160
5.24
4331
5.58
4615
1214
6.00
4960
6.41
5298
1268
6.84
5653
7.31
6047
1324
7.75
6411
8.30
6865
1381
8.75
7239
9.38
7754
1439
9.84
8137
10.54
8715
1497
11.02
9107
11.79
9752
1.8
Bhp
Watts
6.00
6124
6.84
6792
7.75
7524
8.75
8323
Refer to this page for general Fan Performance Data notes.
NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v)
and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm. See Evaporator Fan Motor Perfor-
mance table for more information.
4. Extensive motor and drive testing on these units ensures that the full horse-
power and watts range of the motor can be utilized with confidence. Using
fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire size. Contact your Bryant rep-
resentative for details.
220
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
1171
5.27
4,356
1224
5.80
1218
6.07
5,210
1268
6.63
1266
6.97
5,766
1314
7.55
1315
7.98
6,597
1361
8.58
1365
9.09
7,520
1410
9.72
1417
10.33
8,538
1459
10.98
1469
11.68
9,657
1510
12.36 10,217
1523
13.16 10,883
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
1212
5.65
4675
1262
6.08
1263
6.43
5312
1311
6.86
1315
7.27
6014
1361
7.72
1369
8.20
6782
1413
8.66
1424
9.21
7618
1466
9.68
1480
10.31
8525
1520
10.79
1537
11.50
9504
Watts
4,794
5,478
6,243
7,094
8,037
9,076
Watts
5026
5672
6382
7158
8003
8918