Bryant 580F DuraPac Series Installation, Start-Up And Service Instructions Manual
Bryant 580F DuraPac Series Installation, Start-Up And Service Instructions Manual

Bryant 580F DuraPac Series Installation, Start-Up And Service Instructions Manual

Durapac series sizes 036-073 3 to 6 tons single package rooftop gas heating/electric cooling units
Hide thumbs Also See for 580F DuraPac Series:

Advertisement

IMPORTANT - READ BEFORE INSTALLING
1. Read and become familiar with these installation
instructions before installing this unit (Fig. 1A and
1B).
2. Be sure the installation conforms to all applicable lo-
cal and national codes.
3. These instructions contain important information for
the proper maintenance and repair of this equipment.
Retain these instructions for future use.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-36
I. Step 1 - Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 - Field Fabricate Ductwork . . . . . . . . . . . . . 4
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
IV. Step 4 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 4
V. Step 5 - Install Flue Hood . . . . . . . . . . . . . . . . . . . . 6
VI. Step 6 - Install Gas Piping . . . . . . . . . . . . . . . . . . . 6
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37-47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47-52
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .53-57
APPENDIX A - ECONOMI$ER+ LABEL . . . . . . . . . . . 58, 59
CONFIGURATION SETTINGS . . . . . . . . . . . . . . . . . . . . . 60
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Page
Cancels: II 580F-36-3
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than
1
sures greater than
/
psig will cause gas valve damage
2
resulting in hazardous condition. If gas valve is sub-
jected to pressure greater than
replaced before use. When pressure testing field-
supplied gas piping at pressures of
unit connected to such piping must be isolated by man-
ually closing the gas valve.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install a lockout tag. Electrical shock could
cause personal injury.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply provided for the unit.
INSTALLATION
Unit is shipped in the vertical duct configuration. To convert to
horizontal configuration, remove screws from side duct open-
ing covers and remove covers. Using the same screws, install
covers on vertical duct openings with the insulation-side down.
Seals around duct openings must be tight. See Fig. 2.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.
I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 3. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to the unit. The accessory
thru-the-bottom power and gas connection package must be
installed before the unit is set on the roof curb. If field-
installed (thru-the-roof curb) gas connections are desired, use
3
factory-supplied
/
-in. pipe coupling and gas plate assembly
4
to mount the thru-the-roof curb connection to the roof curb.
Gas connections and power connections to the unit must be
field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service con-
nections to the basepan in accordance with the accessory
installation instructions.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 3. Improperly applied gasket can
result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in
Fig. 4. This is necessary for unit drain to function properly.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
580F
Dura Pac Series
Sizes 036-073
3 to 6 Tons
II 580F-36-4
1/15/04
1
/
psig. Pres-
2
1
/
psig, it must be
2
1
/
psig or less, a
2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 580F DuraPac Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bryant 580F DuraPac Series

  • Page 1: Table Of Contents

    installation, start-up and 580F service instructions Dura Pac Series SINGLE PACKAGE ROOFTOP Sizes 036-073 GAS HEATING/ELECTRIC COOLING UNITS 3 to 6 Tons Cancels: II 580F-36-3 II 580F-36-4 1/15/04 IMPORTANT — READ BEFORE INSTALLING WARNING: Disconnect gas piping from unit when 1.
  • Page 2 — —...
  • Page 3 — —...
  • Page 4: Installation

    Fig. 2 — Horizontal Conversion Panels B. Slab Mount (Horizontal Units Only) III. STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN- SATE DRAIN Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser The unit’s -in.
  • Page 5 ROOF CURB D ALT UNIT SIZE CONNECTOR ACCESSORY ACCESSORY DRAIN POWER CONTROL PKG. ACCY. POWER HOLE 1′-2″ CRRFCURB001A01 ″ [19] NPT [356] CRBTMPWR001A01 580F ″ [19] NPT ″ ″ 036-073 ″ [31.7] 2′-0″ CRBTMPWR002A01 ″ ″ 1′-9 1′-4″ CRRFCURB002A01 [12.7] [12.7] [610] ″...
  • Page 6: Step 5 - Install Flue Hood

    Although unit is weatherproof, guard against water from higher level runoff and overhangs. Flue vent discharge must have a minimum horizontal clear- ance of 4 ft from electric and gas meters, gas regulators, and MAXIMUM ALLOWABLE DIFFERENCE (in.) gas relief equipment. Minimum distance between unit and other electrically live parts is 48 inches.
  • Page 7 3. Unit weights do not include economizer. See Table 1 for economizer weights. NOTES: 1. Dimensions in ( ) are in millimeters. 2. Hook rigging shackles through holes in base rail, as shown in detail “A.” CAUTION: Holes in base rails are centered around the unit center of gravity. Use All panels must be in place when rigging.
  • Page 8 Table 1 — Physical Data UNIT SIZE 580F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* — Cu/Cu* — Economizer EconoMi$er+ Roof Curb† COMPRESSOR Reciprocating Scroll Quantity No. Cylinders (per Circuit) Oil (oz) REFRIGERANT TYPE R-22 Expansion Device Fixed Orifice Metering Device Operating Charge (lb-oz) Circuit 1 6-14...
  • Page 9 Table 1 — Physical Data (cont) UNIT SIZE 580F 072 AND 073 FURNACE SECTION Rollout Switch Cutout Temp (F)†† Burner Orifice Diameter (in..drill size) Natural Gas .113...33 .113...33 .113...33 .113...33 114/115 .113...33 .113...33 .113...33 .113...33 149/150 — .129...30 .129...30 .129...30 060N .102...38...
  • Page 10: Step 7 - Make Electrical Connections

    18 AWG cannot be directly connected to B. Field Control Wiring the thermostat and will require a junction box and splice at Install a Bryant-approved accessory thermostat assembly the thermostat. according to installation instructions included with the Pass the control wires through the hole provided in the cor- accessory.
  • Page 11 208/230-3-60 208/230-1-60 460-3-60 (SIZES 072 AND 073) 575-3-60 208/230-3-60 (SIZES 072 AND 073) 575-3-60, 460-3-60 (SIZES 036-060) LEGEND — Contactor COMP — Compressor — Indoor-Fan Contactor — National Electrical Code — Terminal Block Fig. 9 — Power Wiring Connections RACEWAY LOW VOLTAGE INTEGRATED GAS UNIT COOL STAGE 1...
  • Page 12 Table 2A — Electrical Data (Without Convenience Outlet) VOLTAGE COMPR DISCONNECT COMBUSTION POWER SUPPLY UNIT NOMINAL RANGE (ea) (ea) SIZE* FAN MOTOR 580F VOLTAGE TYPE MOCP† 25.2/25.2 30/30 24/24 106/106 208/230-1-60 16.2 96.0 26.6/26.6 35/35 26/26 111/111 17.7/17.7 25/25 17/17 85/ 85 208/230-3-60 10.2...
  • Page 13 Table 2B — Electrical Data (With Convenience Outlet) VOLTAGE COMPR DISCONNECT COMBUSTION POWER SUPPLY UNIT NOMINAL RANGE (ea) (ea) SIZE* FAN MOTOR 580F VOLTAGE TYPE MOCP† 31.2/31.2 35/35 30/30 111/111 208/230-1-60 16.2 96.0 32.6/32.6 40/40 31/31 116/116 22.5/22.5 25/25 23/23 90/ 90 208/230-3-60 10.2...
  • Page 14: Step 8 - Adjust Factory-Installed Options

    VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS 6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper. A. Manual Outdoor-Air Damper 7. Align screw holes on hood with screw holes on side of The outdoor-air hood and screen are attached to the basepan manual outdoor-air damper.
  • Page 15 B. Optional EconoMi$er+ Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is See Fig. 16 for EconoMi$er+ component locations. shown in Fig. 25. NOTE: These instructions are for the factory-installed optional EconoMi$er+ only.
  • Page 16 17 1/4” PANEL INDOOR COIL ACCESS PANEL DIVIDER LEFT HOOD SCREW OUTSIDE SIDE 19 1/16” HOOD 33 3/8” CLEANABLE ALUMINUM FILTER FILTER HOOD DIVIDER BAROMETRIC Fig. 20 — Outdoor-Air Hood Construction RELIEF FILTER CLIP Fig. 21 — Filter Installation (FIELD-SUPPLIED) LEGEND ECON —...
  • Page 17 temperature is above the set point then the EconoMi$er should be in minimum position. If the outdoor air tempera- 2500 ture is below the set point, the position should be controlled to maintain the leaving air temperature set point. The set 2000 point range is 45 to 70 F.
  • Page 18 Table 3 — EconoMi$er+ Sensor Usage ACCESSORY ACCESSORY INDOOR STANDARD OUTDOOR AIR ACCESSORY RETURN AIR APPLICATION OUTDOOR AIR RETURN AIR TEMPERATURE SENSOR TEMPERATURE SENSOR HUMIDITY SENSOR HUMIDITY SENSOR Standard Unit Included — HH79NZ039 — — — Differential Required — Included — HH79NZ039 —...
  • Page 19 The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section. ECONOMI$ER+ CONTROLLER Mount return temperature sensor HOOD EconoMi$er+, through pre-punched holes. See Fig. 27. The return air temperature (RAT) sensor is provided with a ACTUATOR 2-wire, 42-in.
  • Page 20 Table 5 — Outdoor Air, Return Air, and Supply Air Temperature Sensors (CRTEMPSN001A00 or HH79NZ039) — 10K Thermistor Curve TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE ohms ohms ohms 248.0 390.0 150.8 2,011.0 53.6 18,090.0 246.2 401.2 149.0 2,083.0 51.8 18,972.0 244.4 412.8 147.2...
  • Page 21 Fig. 29 — Enthalpy Changeover Settings CURRENT RH (%) (mA) 10.4 12.0 13.6 15.2 16.8 18.4 HUMIDITY IN % RH RH — Relative Humidity Fig. 30 — Humidity Sensor Current vs. Humidity — —...
  • Page 22 L. Indoor Air Humidity Sensor ECONOMI$ER+ CONTROLLER For differential enthalpy sensing, the EconoMi$er+ control- ler uses the standard outdoor air temperature sensor, the outdoor air humidity sensor, and the optional indoor air ECONOMI$ER+ humidity sensor, an optional return air temperature sensor (RAT).
  • Page 23 minimum position (configuration item number 15), unless S. Dehumidification of Fresh Air with Demand Control Ven- the remote potentiometer is used to override it. tilation (DCV) For the demand ventilation control logic, the user configures Information from ASHRAE (American Society of Heating, the lower and upper actuator position to establish the base Refrigeration and Air Conditioning Engineers) indicates that ventilation rate (IAQMIN_SP) and the design ventilation...
  • Page 24: Step 9 - Adjust Evaporator-Fan Speed

    IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED Adjust evaporator-fan rpm to meet jobsite conditions. Table 8 shows fan rpm at motor pulley settings. Table 9 shows motor performance. Refer to Tables 10-33 to determine fan speed settings. A. Direct-Drive Motors The evaporator-fan motor factory speed setting is shown on label diagram affixed to base unit.
  • Page 25 Table 8 — Fan Rpm at Motor Pulley Settings* MOTOR PULLEY TURNS OPEN UNIT 580F 036† 1045 1009 — — 036** 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 048† 1175 1135 1094 1054 1013 —...
  • Page 26 Table 11 — Fan Performance 580F036 — Vertical Discharge Units, Alternate Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 0.15 0.22 0.30 0.37 1037 0.46 1000 0.19 0.27 0.35 0.43 1069 0.52 1100 0.24 0.32 0.41...
  • Page 27 Table 14 — Fan Performance 580F048 — Vertical Discharge Units, Alternate Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 1200 0.26 0.37 0.47 0.57 1025 0.67 1300 0.31 0.43 0.54 0.65 1053 0.76 1400 0.36 0.49...
  • Page 28 Table 16 — Fan Performance 580F060 — Vertical Discharge Units, Standard Motor STANDARD MOTOR (DIRECT DRIVE) Low Speed Medium Speed High Speed Airflow 208 V 230,460,575 V 208 V 230,460,575 V 208 V 230,460,575 V (Cfm) Watts Watts Watts Watts Watts Watts 1500...
  • Page 29 Table 18 — Fan Performance 580F060 — Three-Phase, Vertical Discharge Units, Alternate Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 1500 0.42 0.55 1006 0.70 1088 0.87 1163 1.05 1600 0.49 0.63 1038 0.78 1119 0.95...
  • Page 30 Table 20 — Fan Performance 580F072,073 — Vertical Discharge Units, Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 1800 0.65 1077 0.81 1172 0.96 1257 1.12 1334 1.27 1130 1900 1007 0.75 1115 0.91 1208...
  • Page 31 Table 22 — Fan Performance 580F036 — Horizontal Discharge Units, Standard Motor STANDARD MOTOR (DIRECT DRIVE) Low Speed High Speed Airflow 208 V 230, 460, 575 V 208 V 230, 460, 575 V (Cfm) Watts Watts Watts Watts 0.54 0.21 0.57 0.23 0.55...
  • Page 32 Table 25 — Fan Performance 580F048 — Horizontal Discharge Units, Standard Motor STANDARD MOTOR (DIRECT DRIVE) Low Speed High Speed Airflow 208 V 230, 460, 575 V 208 V 230, 460, 575 V (Cfm) Watts Watts Watts Watts 1200 0.75 0.41 0.81 0.45...
  • Page 33 Table 27 — Fan Performance 580F048 — Horizontal Discharge Units, High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 1200 0.23 0.34 0.46 0.58 1020 0.71 1300 0.28 0.40 0.52 0.65 1044 0.78 1400 0.33 0.45...
  • Page 34 Table 29 — Fan Performance 580F060 — Single-Phase, Horizontal Discharge Units, Alternate Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 1500 0.40 0.53 0.67 1074 0.83 1151 1.00 1600 0.46 0.60 1021 0.75 1103 0.91 1179...
  • Page 35 Table 31 — Fan Performance 580F060 — Horizontal Discharge Units, High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 1500 0.40 0.53 0.67 1074 0.83 1151 1.00 1600 0.46 0.60 1021 0.75 1103 0.91 1179 1.09...
  • Page 36 3. Use of a field-supplied motor may affect wire sizing. Contact your 2. Extensive motor and electrical testing on these units ensures that Bryant representative for details. the full range of the motor can be utilized with confidence. Using 4. Interpolation is permissible. Do not extrapolate.
  • Page 37: Pre-Start-Up

    PRE-START-UP sure Start-Up Checklist on back page is filled out and completed. WARNING: Failure to observe the following warnings II. RETURN-AIR FILTERS could result in serious personal injury. 1. Follow recognized safety practices and wear protective Make sure correct filters are installed in filter tracks. See goggles when checking or the servicing refrigerant Table 1.
  • Page 38 0 seconds and the OFF delay can be extended *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. †Orifices are available through your local Bryant distributor. — —...
  • Page 39 XII. SAFETY RELIEF that the control is being initialized. The buttons are not operational during Startup mode. A soft solder joint at the suction service Schrader port pro- vides pressure relief under abnormal temperature and pres- C. Run Mode sure conditions (i.e., fire in building). Run mode indicates status of controller and unit.
  • Page 40 ADVANCE READ/ MANUAL ADJUST date or serial no RED YELLOW GREEN SETPOINT DISPLAY PUSH BUTTONS Relays rated at 24 VAC 3A and traces for 8A. NOTE: For 1 and 2 stage 24 VAC cooling, 2 stages of power exhaust will be used. Y1 (cool 1) 24 VAC For 3 cooling stages, only 1...
  • Page 41 Table 36 — Start-Up Mode Sequence TIME LED 1/DS1 (RED) LED 2/DS2 (YELLOW) LED 3/DS3 (GREEN) LED 4/DS4 (GREEN) 0-1.0 SEC 1-1.5 SEC FLASH ½ SEC 1.5-2.0 SEC FLASH ½ SEC 2.0-2.5 SEC FLASH ½ SEC 2.5-3.0 SEC FLASH ½ SEC LED —...
  • Page 42 After advancing through all the configuration variables in Verify what Setup Point is being read by pushing the READ/ the Read mode, the controller will then advance through the ADJUST button (#1). First the Red LED will flash the set status of the I/O channels.
  • Page 43 6. Verify the configuration point by pushing button #1. Enter the Manual mode by holding down the ADVANCE/ The red LED should flash twice to indicate point 2, MANUAL (#2) button for at least 3 seconds until all LEDs and then the green LEDs will flash the current flash and then the red LED comes on steady.
  • Page 44 IMPORTANT: There is no way to reset/restore the factory B. Ventilation Air and Free Cooling default configurations; use caution when making changes to In order for the EconoMi$er+ to control ventilation air and any set point or operational variable. free cooling, several items must be configured. The EconoMi$er+ control accepts an occupied/unoccupied EconoMi$er+ Type switch input.
  • Page 45 Compressor Lockout Temperature generated by all sources including people at the design value for maximum occupancy. Set the Compressor Lockout Temperature. The Compressor Lockout Temperature (CMP_LOCK) is used to prevent com- A reference differential CO level above the outside CO pressor from running at low ambient conditions when an level is used as the starting point for IAQ control and EconoMi$er+ can easily satisfy the load.
  • Page 46 while the unit is in cooling. When the thermostat is satisfied, If the unit is in the unoccupied mode, then the control of the C is deenergized and the compressor and OFM shut off. After temperature will depend on the unoccupied free cooling a 30-second delay, the (IFM) shuts off.
  • Page 47: Service

    As an example, if local codes require 10% outdoor air during outer coil section 3 to 4 in. from the inner coil section. occupied conditions, outdoor-air temperature is 60 F, and See Fig. 39. return-air temperature is 75 F: 6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and (60 x 0.10) + (75 x 0.90) = 73.5 F debris.
  • Page 48 Fig. 40 — Condenser-Fan Adjustment A. No Charge Use standard evacuating techniques. After evacuating sys- Fig. 39 — Separating Coil Sections tem, to 500 microns, weigh in the specified amount of refrig- erant. (Refer to Table 1.) B. Low-Charge Cooling II.
  • Page 49 A complete list of replacement parts may be obtained from 9 Flashes Internal Software Processor Fault any Bryant distributor upon request. LEGEND LED — Light-Emitting Diode *A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.
  • Page 50 3 TON UNIT CHARGING CHART SUCTION LINE TEMPERATURE (DEG. C) OUTDOOR TEMP SUCTION LINE TEMPERATURE (DEG. F) Fig. 41 — Cooling Charging Chart, 580F036 4 TON UNIT CHARGING CHART SUCTION LINE TEMPERATURE (DEG. C) OUTDOOR TEMP SUCTION LINE TEMPERATURE (DEG. F) Fig.
  • Page 51 5 TON UNIT CHARGING CHART SUCTION LINE TEMPERATURE (DEG. C) OUTDOOR TEMP SUCTION LINE TEMPERATURE (DEG. F) Fig. 43 — Cooling Charging Chart, 580F060 6 TON UNIT (60 Hz) CHARGING CHART SUCTION LINE TEMPERATURE (DEG. C) OUTDOOR TEMP SUCTION LINE TEMPERATURE (DEG. F) Fig.
  • Page 52: Service

    INDUCED- ROLLOUT DRAFT SWITCH MOTOR MOUNTING PLATE BURNER SECTION FLUE EXHAUST VESTIBULE PLATE INDUCED- Fig. 46 — Burner Tray Details DRAFT BLOWER MOTOR HOUSING MANIFOLD PRESSURE VALVE Fig. 45 — Burner Section Details LOW HEAT 580F036-073 — 74,000 BTUH INPUT 580F036-060 (Low NO ) —...
  • Page 53: Troubleshooting

    TROUBLESHOOTING C. Error Code 3 — OAT Sensor Failure Error Criteria I. ECONOMI$ER+ TROUBLESHOOTING An OAT Sensor Failure error occurs if the sensor is shorted The EconoMi$er+ control has built-in diagnostics. The con- or faulty, then the measured temperature will be below trol can detect and display 10 different diagnostic codes as –40 F or above 250 F.
  • Page 54 Reset Method NOTE: Cycling power to the board will also erase the repaired error codes. This error must be manually reset and requires a power reset. J. RAM Test Failure H. Error Code 8 — E2 Test Failure Error Criteria Error Criteria If internal hardware detects a RAM failure, this alarm will displayed...
  • Page 55 Table 41 — LED Error Code Service Analysis SYMPTOM CAUSE REMEDY Hardware Failure. Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and (LED OFF) transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer.
  • Page 56 Table 43 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and Condenser Fan Power failure. Call power company. Will Not Start. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Defective thermostat, contactor, transformer, or Replace component. control relay.
  • Page 57 NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 2. Three phase motors are protected under primary single phasing conditions. 4. Use copper conductors only. 6.
  • Page 58: Appendix A - Economi$Er+ Label

    APPENDIX A — ECONOMI$ER+ LABEL — —...
  • Page 59: Appendix A — Economi$Er+ Label

    APPENDIX A — ECONOMI$ER+ LABEL (cont) — —...
  • Page 60: Appendix B - Job Specific Economi$Er+ Configuration Settings

    APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURATION SETTINGS Enter the job specific settings in the “Job Setting” column below. — —...
  • Page 61: Index

    INDEX Access panels Low pressure switch 9, 49 Altitude compensation Main burners 38, 49 Barometric flow capacity Manual outdoor air damper Burner ignition Mounting Burner rack Compressor Burner section Unit Burner spark gap Natural gas Charging chart, refrigerant Operating limits 50, 51 Clearance Operating sequence...
  • Page 62 Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-644-5544 [ ] Packaged Service Training [ ] Classroom Service Training Copyright 2004 Bryant Heating & Cooling Systems CATALOG NO. 5358-023...
  • Page 64: Start-Up Checklist

    TEMP ° F REFRIGERANT DISCHARGE ____________ PSIG ____________ TEMP ° F VERIFY REFRIGERANT CHARGE USING CHARGING TABLES VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION (580F072 AND 073 ONLY) CL-1 Copyright 2004 Bryant Heating & Cooling Systems CATALOG NO. 5358-023...

Table of Contents