Bryant 579F User Manual page 191

Durapac and durapac plus series commercial single package rooftop units gas heating/electric cooling units
Table of Contents

Advertisement

579F180230 (15 TONS) *
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
4500
809
1.53
4800
850
1.76
5100
892
2.01
5400
934
2.28
5700
976
2.58
6000
1019
2.90
6300
1063
3.24
6600
1106
3.61
6900
1150
4.00
7200
7500
579F180230 (15 TONS)* (cont)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
4500
1301
2.87
4800
1324
3.13
5100
1349
3.41
5400
1374
3.71
5700
1402
4.04
6000
6300
6600
6900
7200
7500
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Standard low-medium static drive range is 891 to 1179 rpm (208/230 v and
460 v) or 1159 to 1429 (575 v). Alternate high-static drive range is 1227 to 1550
(208/230 v and 460 v only). Other rpms require a field-supplied drive.
579F216275 AND 240275 (18 AND 20 TONS) *
Airflow
0.2
(Cfm)
Rpm
Bhp
Watts
5,500
755
2.27
6,000
810
2.72
6,500
866
3.22
7,000
923
3.78
7,500
980
4.39
8,000
1038
5.06
8,500
1096
5.78
9,000
1154
6.56
9,500
1213
7.40
10,000
1272
8.30
579F216275 AND 240275 (18 AND 20 TONS)* (cont)
Airflow
1.4
(Cfm)
Rpm
Bhp
Watts
5,500
1149
4.28
6,000
1183
4.76
6,500
1219
5.29
7,000
1258
5.88
7,500
1299
6.52
8,000
1341
7.21
8,500
1385
7.97
9,000
1431
8.78
9,500
1478
9.65
10,000
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Standard low-medium static drive range for the 216 size is 910 to 1095 rpm.
Standard low-medium static drive range for the 240 size is 1002 to 1225 rpm.
Alternate high-static drive range for the 216 size is 1069 to 1287. Alternate high-
static drive range for the 240 size is 1193 to 1458 rpm. Other rpms require a field-
supplied drive.
PERFORMANCE DATA — 579F (cont)
FAN PERFORMANCE — 579F180-300 UNITS
Available External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
1317
906
1.74
1502
994
1516
942
1.98
1706
1027
1733
979
2.24
1928
1061
1970
1017
2.52
2169
1096
2225
1056
2.82
2429
1132
2500
1096
3.14
2709
1168
2795
1136
3.49
3008
1206
3111
1177
3.86
3329
1244
3448
1218
4.26
3670
Available External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
2477
1369
3.11
2683
1434
2700
1390
3.37
2909
1454
2942
1413
3.66
3153
1475
3202
1437
3.96
3416
1498
3481
1463
4.29
3699
Available External Static Pressure (in. wg)
0.4
Rpm
Bhp
Watts
Rpm
1908
831
2.58
2171
901
2287
881
3.04
2556
947
2710
932
3.55
2985
994
3177
985
4.11
3458
1044
3690
1038
4.73
3976
1094
4251
1093
5.40
4542
1146
4859
1148
6.13
5156
1198
5517
1204
6.92
5818
1251
6224
1260
7.77
6531
1306
6983
1317
8.67
7294
1360
Available External Static Pressure (in. wg)
1.6
Rpm
Bhp
Watts
Rpm
3602
1204
4.65
3907
1258
4003
1236
5.13
4310
1288
4450
1270
5.66
4759
1320
4942
1307
6.25
5253
1355
5480
1346
6.89
5794
1392
6065
1387
7.59
6383
1392
6699
1429
8.35
7019
1472
7382
1473
9.15
7705
1515
8114
1519
10.04
8441
0.6
0.8
Bhp
Watts
Rpm
Bhp
Watts
1.96
1690
1078
2.18
1882
2.20
1899
1107
2.43
2094
2.46
2125
1138
2.70
2325
2.75
2371
1170
2.99
2575
3.06
2635
1204
3.30
2843
3.38
2919
1238
3.63
3131
3.74
3223
1273
3.99
3439
4.11
3547
1309
4.37
3767
1.8
1.9
Bhp
Watts
Rpm
Bhp
Watts
3.35
2891
1497
3.47
2997
3.62
3120
1515
3.74
3226
3.90
3367
1535
4.03
3475
4.21
3633
Refer to page 194 for general Fan Performance Data notes.
NOTE: Maximum continuous bhp is 4.25 (208/230 v and 460 v) or 3.45 (575 v)
and the maximum continuous watts are 3775 (208/230 v and 460 v) or 3065
(575 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating cfm.
0.6
0.8
Bhp
Watts
Rpm
Bhp
Watts
2.91
2443
968
3.24
2723
3.37
2833
1010
3.71
3116
3.88
3266
1054
4.23
3554
4.45
3744
1100
4.80
4036
5.07
4267
1148
5.43
4564
5.75
4838
1197
6.11
5138
6.49
5456
1247
6.85
5761
7.28
6123
1298
7.65
6432
8.13
6840
1350
8.51
7154
9.05
7608
1403
9.43
7926
1.8
1.9
Bhp
Watts
Rpm
Bhp
Watts
5.02
4217
1284
5.20
4375
5.50
4622
1313
5.68
4780
6.03
5073
1344
6.22
5232
6.62
5569
1378
6.81
5729
7.27
6113
1415
7.46
6273
7.97
6704
1453
8.16
6866
8.73
7343
1493
8.93
7506
9.55
8032
1535
9.75
8196
Refer to page 194 for general Fan Performance Data notes.
NOTE: Maximum continuous bhp for the 216 size is 5.90. Maximum continuous
bhp for the 240 size is 8.70 (208/230 and 575 v) or 9.50 (460 v). The maximum
continuous watts for the 216 size is 5180. The maximum continuous watts for the
240 size is 7915 (208/230 and 575 v) or 8640 (460 v). Do not adjust motor rpm
such that motor maximum bhp and/or watts is exceeded at the maximum operat-
ing cfm.
191
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
1156
2.41
2077
1230
2.64
1183
2.66
2293
1255
2.89
1211
2.93
2528
1281
3.17
1241
3.22
2781
1309
3.47
1272
3.54
3053
1338
3.79
1304
3.88
3345
1368
4.13
1337
4.24
3657
2.0
Rpm
Bhp
Watts
1497
3.60
3103
1515
3.87
3334
1535
4.16
3584
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
1031
3.58
3009
1091
3.93
1070
4.05
3406
1127
4.40
1111
4.57
3847
1166
4.93
1155
5.15
4333
1207
5.51
1200
5.78
4864
1250
6.15
1246
6.47
5443
1294
6.84
1294
7.22
6070
1340
7.59
1343
8.02
6745
1388
8.40
1394
8.88
7471
1436
9.26
1445
9.81
8247
1486
10.19
2.0
Rpm
Bhp
Watts
1309
5.39
4533
1337
5.87
4939
1368
6.41
5391
1402
7.00
5890
1437
7.65
6435
1475
8.36
7300
1514
9.12
7670
Watts
2275
2495
2733
2990
3266
3562
Watts
3302
3702
4146
4635
5170
5752
6382
7062
7791
8570

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

581a581b581c580f

Table of Contents