This menu gives you the following setting options:
• Bus address, menu item 4.1.1
The address 126 (factory setting) is reserved for newly connected devices and must be
changed to a smaller value at the latest after commissioning on the bus. A value between 30
and 125 is recommended because addresses below 30 are only assigned for bus masters as
a rule.
An address < 126 is only addressable when no cyclic communication is taking place and all
acyclic connections are closed.
With the PROFIBUS variable "factory_reset = 2712" the address can be reset to the factory
setting 126.
Note
Each address may only be assigned for one device on the connected bus!
• Ident No., menu item 4.1.2
The device profile for the cyclic data traffic can be selected here.
You have the following options:
– Profile-specific (=Ident No. 0x9740) means:
– Manufacturer-specific (= Ident No. 0x80C4) means:
TRANSMAG 2 with MAG 911/E
Operating Instructions, 03/2021, A5E00102775-AC
Restricted functions; i.e. only cyclic parameters according to profile 3.0 (flow and totalizer
net).
Full functions, i.e. cyclic parameters according to profile 3.0 and additional manufacturer-
specific parameters (e.g. totalizer forwards, totalizer reverse).
Note
The connected PROFIBUS master must be configured with a device database file (GSD)
according to the set ID No.
See also Device Database File (GSD) (Page 114)
8.5 Function Group Device Outputs
Functions
67