8.4 Function Group Measuring Functions
Figure 8-3
1. Hysteresis (3.1.5.3). The limit values (menu items 3.1.5.1 and 3.1.5.2) can have a hysteresis
added to prevent "fluttering" of the switching output.
This setting is made in % of the set full scale value in the menu item 3.1.5.3 "Hysteresis". If,
for example, the hysteresis is 1 %, the relay contact does not switch until a flow of -1% of the
full scale value and returns to the original position at a flow of +1% of the full scale value.
Table 8-2
- Contact closes:
- Contact opens:
• Low flow cut, menu item 3.1.6
This parameter determines the switching point for low flow cut-off. The low flow cut prevents
flow being measured in the lower range (e.g. fluctuating liquid columns at a standstill). The
low flow cut-off affects: display, totalizers, analog output and pulse frequency output as well
as HART and PROFIBUS communication.
– In devices with HART communication, the value of the low flow is related percentage-wise
– In devices with PROFIBUS communication, the absolute value must be entered in the
• Filter time constant, menu item 3.1.7.1
The jump response can be suppressed in this menu item. This may be necessary depending
on the application, for example in the case of fast changing flows to keep the display value
or analog value stable.
60
-1
0
b
Reverse
Forwards
Flow in % of range
Hysteresis flow direction
Switching status of the relay for selected signal type
to the upper range value (menu item 3.1.2).
selected unit of flow (menu item 3.1.1).
+1
a
a →
Relay contact closed
b →
Relay contact open
a →
Relay contact open
b →
Relay contact closed