Parameters
6.5
Control Values
6.5.1
Volt. Um
Volt. Uref
6.5.2
Volt. Usig
6.5.3
Volt. Uel1
6.5.4
Volt. Uel2
6.5.5
Flow % Range
6.5.6
Sampl. Frequ.
6.5.7
Selftest
0 %
FS
6.5.8
Service Info
6.5.9
Digital Input
6.6
Zero Trim
6.6.1
Zero Flow Cor.
6.6.2
Start Correct.
6.7
Trim Parameter
6.7.1
Cal.factor
6.7.2
CFH
5
CFR
5
6.7.3
ZPH
5
102
Control value for magnetic field current
Control value for reference voltage
Electrode differential voltage
Control value for voltage between elec‐
trode 1 and medium
Control value for voltage between elec‐
trode 2 and medium
Actual flow in % of set full scale value
1,2
Actual measuring frequency
Display of internal control values of meas‐
uring electronics. Run self-test to update
(menu 2.4.1)
Zero
Gain
Coded service information
Status of the digital input under considera‐
2
tion of the set signal type
Correction value for the zero point of the
flow measurement in m/s
Start of zero calibration; The medium must
be at a standstill during
calibration!
Values in 6.7.2.4 can only be written if no
SmartPlug data can be read
User-specific calibration factor; the meas‐
ured flow value is multiplied by this factor
before output (affects all outputs, totalizers
and display)
Calibration value for hydraulic reference
point at 1m/s
Calibration value for reference path
Calibration value for
hydraulic zero point
(Approx. 2 x
magnetic
frequency)
(Result display of the
Triggered when select‐
last self-test)
ing menu 2.4.1
(xxxxxxxx)
(Current status
active/inactive)
(Info)
(Actual status
active/inactive)
-1 ... +1 m/s
Cancel
•
•
1.0
0.5 ... 1.5
400
100
0
TRANSMAG 2 with MAG 911/E
Operating Instructions, 03/2021, A5E00102775-AC
Cancel
Start