Siemens SITRANS F TRANSMAG 2 Operating Instructions Manual page 97

Electromagnetic flometers
Table of Contents

Advertisement

3.1.5.1
Flow Direction
3.1.5.2
Meas.Direction
3.1.5.3
Hysteresis
3.1.6
Low flow cut
3.1.7
Noise filter
3.1.7.1
Fltr.Time Con.
3.1.7.2
Line Synchron.
3.1.7.3
Noise Suppress
Suppress Time
Suppress Limit
3.1.8
Slurry mode
3.2
Total. Forw.
3.2.1
Set forward
3.2.2
Engr. Unit
3.2.3
Alarm Limit
3.3
Total. rev.
3.3.1
Set reverse
TRANSMAG 2 with MAG 911/E
Operating Instructions, 03/2021, A5E00102775-AC
Main flow direction related to direction ar‐
row on measuring tube (= forwards, posi‐
tive flow values)
Output of suppression of reverse flow
Affects all outputs, totalizers and display
Hysteresis of detection of flow direction in
% of full scale value
Threshold for low flow cut in % of full scale
value 1, 2 or absolute value in flow unit 3
Time constant τ for measured value attenu‐
ation; after a jump in
the measuring variable, the output meas‐
ured value reaches about 99% of the new
setpoint after 5*τ
Does not affect totalizers.
Values outside a tolerance range are evalu‐
ated for the duration of the blanking time
with high attenuation.
Time of effect of increased attenuation (0 s
= blanking off)
Tolerance range = floating average + toler‐
ance value
This is used when signals are severely im‐
paired, e.g. for media with a high solids
content or air locks
Totalizer forwards
Reset totalizer to zero and stop or start
Engineering unit of volume
or
Engineering unit of mass When you select a
unit of mass, entry of the actual medium
density is mandatory (menu 3.1.4)
Totalizer reverse
Reset totalizer to zero and stop or start
+Direction
+Direction,
-Direction
forw.+rev.
forward only,
forw.+rev.
0.2 %
0 to 20 %
1 %
0 to 20 %
3.00 s
0.0 ... 200.0 s
Auto mode
Not available
0 s
0 ... 100
0 %
0 ... 100
Off
On
Off
Cancel 1,2
Cancel 1,2,
Totalize 3
Reset+Stop,
Reset+Start 1,2,
Totalize 3
DN 2...12: l
l, hl, m3, Ml, ft3, Gal,
MGal, ImpGal, MImpGal
DN >12: m3
kg, t, g, lb
+1000000 l
-108 ... +108
Cancel 1,2
Cancel 1,2,
Totalize 3
Reset+Stop,
Reset+Start 1,2,
Totalize 3
Parameters
97