TrueNet
1U and 2U Fiber Panel
Installation and Cable Routing Instructions
ADCP-92-082 • Issue 2 • 10/2008
Selecting a Mounting Bracket Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installing the Panel on the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installing Vertical Cable Guides (VCGs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Sliding the Drawer In and Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Grounding the Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
22049-A
(continued)
Page 1
© 2008, ADC Telecommunications, Inc.
Page

Advertisement

Table of Contents
loading

Summary of Contents for ADC TrueNet 1U

  • Page 1: Table Of Contents

    Grounding the Panel ............. . 10 (continued) 1455459 Rev A Page 1 © 2008, ADC Telecommunications, Inc.
  • Page 2: Introduction

    CUSTOMER INFORMATION AND ASSISTANCE ........... 26 INTRODUCTION This manual contains descriptions and installation and cable routing instructions for the ADC TrueNet 1U and 2U Fiber Panels.
  • Page 3: Description

    1 DESCRIPTION The TrueNet 1U and 2U Panels can accommodate up to 48 and 96 terminations, respectively. The TrueNet 1U and 2U Panels can be configured for termination and splice or termination only (without splice trays). Figure 1 shows the external features of a typical 1U panel.
  • Page 4: Installation

    Section 2.6 on Page 11); 5. (Optional) Installing MPO cassettes (covered in Section 2.7 on Page 12); 6. Installing a cable clamp (covered in Section 7. Routing cables and pigtails (covered in Section Page 4 © 2008, ADC Telecommunications, Inc.
  • Page 5: Selecting A Mounting Bracket Option

    ROTATE BRACKET FOR 23-INCH RACK MOUNTING 1U FIBER PANEL 5 INCH RACK RECESS POSITION (AS SHIPPED) ROTATE BRACKET FOR 23-INCH RACK MOUNTING 2U FIBER PANEL 22052-A Figure 3. Selecting a Mounting Bracket Option Page 5 © 2008, ADC Telecommunications, Inc.
  • Page 6: Installing The Panel On The Rack

    1U and 2U fiber panels installed in a 19-inch rack with a 5-inch recess. 12-24 SCREWS (4 PLACES) 12-24 SCREWS (4 PLACES) 22050 -A Figure 4. Installing the Panel on the Rack Page 6 © 2008, ADC Telecommunications, Inc.
  • Page 7: Installing Vertical Cable Guides (Vcgs)

    HOLES FOR VCG 6-32 SCREWS (2 PER VCG) (PROVIDED) 1U FIBER PANEL VCG (2) 22051-A INSTALLATION 2U FIBER PANEL 6-32 SCREWS HOLES FOR VCG (2 PER VCG) (PROVIDED) Figure 5. Installing Vertical Cable Guides Page 7 © 2008, ADC Telecommunications, Inc.
  • Page 8: Sliding The Drawer In And Out

    Figure 8. Slide the drawer in until it locks into the closed position. 22100-A PRESS BUTTON DOWN TO PULL TRAY OUT TO FIRST DETENT Figure 6. Releasing Closed Drawer to Open It Page 8 © 2008, ADC Telecommunications, Inc.
  • Page 9 Figure 7. Freeing Drawer to Slide It Out Fully 22102-A PRESS IN TRAY RETAINER CLIPS (ONE ON EACH SIDE) TO SLIDE TRAY BACK INTO PLACE Figure 8. Releasing Open Drawer to Close It Page 9 © 2008, ADC Telecommunications, Inc.
  • Page 10: Grounding The Panel

    23126-A GROUNDING LOCATIONS Figure 9. Grounding Locations (Rear View of Panel) 2-HOLE LUG TERMINAL COPPER WIRE HOLE CENTER SPACING: 0.75 INCHES STRIP BACK INSULATION 23127-A PER LUG MANUFACTURER'S RECOMMENDATION Figure 10. Ground Stud Page 10 © 2008, ADC Telecommunications, Inc.
  • Page 11: Installing Adapter Packs

    "IN" TO LOCK ADAPTER PACK INTO PANEL "IN" "OUT" POSITION POSITION NYLATCH PLUNGER FASTENERS MUST BE PULLED OUT BEFORE INSERTING THE ADAPTER PACK INTO MOUNTING HOLES 21568-B IN PANEL Figure 11. Installing Adapter Packs Page 11 © 2008, ADC Telecommunications, Inc.
  • Page 12: Installing Mpo Cassettes

    LOCK CASSETTE INTO PANEL ARE PULLED OUT "IN" POSITION "OUT" POSITION NYLATCH PLUNGER FASTENERS MUST BE PULLED OUT BEFORE INSERTING THE MPO CASSETTES INTO MOUNTING HOLES IN PANEL. 22059-A Figure 12. Installing MPO Cassettes Page 12 © 2008, ADC Telecommunications, Inc.
  • Page 13: Cable Clamp Installation

    LATCH (2) LEFT SIDE OSP CABLE ENTRANCE 22055-A SCREW (2) GROMMET (SIZE DETERMINED YOKE (2) BY DIAMETER OF OSP CABLE) PLATE RIGHT SIDE OSP CABLE ENTRANCE Figure 13. Cable Clamp Assembly for OSP Cable Page 13 © 2008, ADC Telecommunications, Inc.
  • Page 14: Installing A Cable Clamp For Mpo Trunk Cable

    Note: This procedure requires use of the MPO trunk cable clamp kit, which can be ordered from ADC using catalog # TFP-ACC002. This kit is required for routing MPO trunk cable in panels with MPO adapter packs. This kit may also be used for routing MPO trunk cable in panels with MPO cassettes, but the kit is not required for MPO cassette applications.
  • Page 15: Cable Routing Procedures

    IF NECESSARY, PULL EACH 900 MICRON FIBER FROM CORRECT LENGTH AT ADAPTER PACK STUB END OF SUBUNIT, TO CORRECT LENGTH TO 22072-A ELIMINATE SLACK AT ADAPTER PACK. Figure 15. Routing Pigtails from Right Side (Top View) Page 15 © 2008, ADC Telecommunications, Inc.
  • Page 16: Routing Osp Cable, Right Side Entry

    For right side cable entry, route the OSP cable from the cable clamp position to the splice tray as shown in Figure 17. Note that “right” is defined here from the perspective of the front of the panel. Page 16 © 2008, ADC Telecommunications, Inc.
  • Page 17 LENGTH - 120 INCHES FOR SPLICE TRAY USE VELCRO STRAP ROUTING, SEE (PROVIDED) TO SECURE SECTION 3.2.4, SPLICE TRAY TO PANEL "SPLICE TRAY ROUTING" 22064-A Figure 17. Routing OSP Cable, Right Side Entry Page 17 © 2008, ADC Telecommunications, Inc.
  • Page 18: Routing Osp Cable, Left Side Entry

    LENGTH - 120 INCHES FOR SPLICE TRAY USE VELCRO STRAP ROUTING, SEE (PROVIDED) TO SECURE SECTION 3.2.4, SPLICE TRAY TO PANEL "SPLICE TRAY ROUTING" 22065-A Figure 18. Routing OSP Cable, Left Side Entry Page 18 © 2008, ADC Telecommunications, Inc.
  • Page 19: Routing Pigtails And Osp Fibers In Splice Tray

    FROM ADAPTERS PIGTAIL FIBER ROUTING USE LACING TO SECURE SUBUNIT FIBERS PIGTAIL BREAKOUT SIDE 22066-A OSP FIBER ROUTING USE LACING TO SECURE SUBUNIT Figure 19. Routing Pigtails and OSP Fibers in Splice Tray Page 19 © 2008, ADC Telecommunications, Inc.
  • Page 20: Termination Only Panel Procedures

    LENGTH - 60 INCHES TIE-DOWN TIE-DOWN POINT POINT 22068-A - DRAWER IN CLOSED POSITION NOTE: - TOP COVER NOT SHOWN, FOR CLARITY - REAR COVER REMOVED Figure 20. Routing OSP Cable, Right Side Entry (Adapter Packs) Page 20 © 2008, ADC Telecommunications, Inc.
  • Page 21: Routing Osp Cable, Left Side Entry (Adapter Cassettes)

    EXPOSED TIE-DOWN TIE-DOWN POINT POINT 22067-A - DRAWER IN CLOSED POSITION NOTE: - TOP COVER NOT SHOWN, FOR CLARITY - REAR COVER REMOVED Figure 21. Routing OSP Cable, Left Side Entry (MPO Cassettes) Page 21 © 2008, ADC Telecommunications, Inc.
  • Page 22: Routing Osp Cable, Left Side Entry (Mpo Cassettes)

    PULL OUT THE SLIDING TRAY FOR LEFT SIDE ENTRY 22069-A - DRAWER IN CLOSED POSITION NOTE: - TOP COVER NOT SHOWN, FOR CLARITY - REAR COVER REMOVED Figure 22. Routing OSP Cable, Left Side Entry (MPO Cassettes) Page 22 © 2008, ADC Telecommunications, Inc.
  • Page 23: Routing Osp Cable, Right Side Entry (Mpo Cassettes)

    PULL OUT THE SLIDING TRAY FOR RIGHT SIDE ENTRY 22070-A - DRAWER IN CLOSED POSITION NOTE: - TOP COVER NOT SHOWN, FOR CLARITY - REAR COVER REMOVED Figure 23. Routing OSP Cable, Right Side Entry (Adapter Packs) Page 23 © 2008, ADC Telecommunications, Inc.
  • Page 24: Mpo Termination Only Panel Procedures

    FOR RIGHT SIDE ENTRY 22180-A - DRAWER IN CLOSED POSITION NOTE: - TOP COVER NOT SHOWN, FOR CLARITY - REAR COVER REMOVED Figure 24. Routing MPO Trunk Cable, Right Side Entry (MPO Adapter Packs) Page 24 © 2008, ADC Telecommunications, Inc.
  • Page 25: Routing Mpo Trunk Cable, Left Side Entry (Mpo Adapter Packs)

    FOR LEFT SIDE ENTRY 22181-A - DRAWER IN CLOSED POSITION NOTE: - TOP COVER NOT SHOWN, FOR CLARITY - REAR COVER REMOVED Figure 25. Routing MPO Trunk Cable, Left Side Entry (MPO Adapter Packs) Page 25 © 2008, ADC Telecommunications, Inc.
  • Page 26: Customer Information And Assistance

    ADCP Number: Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages.