AEG ME10 Manual page 79

Power circuit breaker

Advertisement

Time Current Curves (cold state), Protection Device
Auslösekennlinien (aus kaltem Zustand), Schutzgerät
Curve di intervento (a freddo)
ME10 Trip Unit -L, -E, -S, -N, -H & -HE Trip Unit
10000
LT set at Breaker Rating In
2h
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
1000
100
10
1
0,1
1,00
x Breaker Rating In
7.2 x
ME10 Trip Unit -L, -E, -S, -N, -H & -HE Trip Unit
10000
LT set at Breaker Rating In
2h
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
1000
100
10
1
0,1
1,00
x Breaker Rating In
7.2 x
- Time Current Curve
LT- Protection Device
Breaker Type
- Band C-01
- Band C-06
- Band C-09
- Band C-13
- Band C-17
- Band C-20
SD protection - OFF
I protection set to 15 x Ie
10,00
100,00
]
- Time Current Curve
LT- Protection Device
Breaker type
- Band C-03
- Band C-08
- Band C-12
- Band C-16
- Band C-19
SD protection - OFF
I protection set to 15 x Ie
10,00
100,00
TRIP UNIT
ME10 Trip Unit
-E, -S, -N, -H & -HE Trip Unit
10000
LT set at Breaker Rating In
2h
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
1000
100
10
1
0,1
1,00
10,00
x Breaker Rating In
7.2 x
ME10 Trip Unit -L, -E, -S, -N, -H & -HE Trip Unit
10000
LT set at Breaker Rating In
2h
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
1000
100
10
1
0,1
1,00
10,00
x Breaker Rating In
7.2 x
BREAKER ME10
2
.5
- Time Current Curve
LT- Protection Device
Breaker Type
- Band C-02
- Band C-04
- Band C-07
- Band C-14
- Band C-18
- Band C-22
SD protection - OFF
I protection set to 15 x Ie
100,00
]
- Time Current Curve
LT- Protection Device
Breaker Type
- Band C-05
- Band C-09
- Band C-11
- Band C-15
- Band C-21
SD protection - OFF
I protection set to 15 x Ie
100,00
2-35