Download Print this page

AEG ME10 Manual page 20

Power circuit breaker

Advertisement

BREAKER ME10
Table 1.11: Connection options for ME10 in Fixed Mounting Patten
Power Circuit
Breaker type
Envelope T
Envelope 1
Envelope 2
Envelope 3
Table 1.12: Connection options for ME10 in Drawout Mounting Patten
Power Circuit
Breaker type
Envelope T
Envelope 1
Envelope 2
Envelope 3
(1) Cassettes are supplied with a Universal Connection Rear Access Connection..(rotatable, Horizontal or Vertical
..on Envelope 2 the 4000A Cassette has a maximum rating of 3200A when used with horizontal busbars; 4000A with vertical busbars.
..on Envelope 3 the 6400A Cassette has a maximum rating of 5000A when used with horizontal busbars; 6400A with vertical busbars.
(2) Cassettes are available with Horizontal Rear Access Connection or with Universal Rear Access Connection (rotatable, Horizontal or Vertical
English
Cassette available
Envelope
Front access Busbar Connection ............................... Frontseitiger Schienenanschluss .........................................
horizontal or Vertical
Optional
Power Circuit Breaker type ............................................ Leistungsschalter Typ ................................................................
Ratings
Rear Access Horizontal Busbar Connection
Rear access Vertical Busbar Connection
Rear access Vertical ONLY Busbar Connection
Remarks .................................................................................. Hinweise ...........................................................................................
Standard
The Envelope 2 type cassette is supplied with ..
Universal Connection Rear Access Connections Universalanschluss rückseitige Verbindung
Universal Rear Access Busbar Connection ............. Universalanschluss rückseitige Schienenverbindung ..
When used horizontally it has a maximum rating of.. Bei horizontalem Gebrauch maximal Wert von..
When used vertically it has ..
1.2-06
INTRO
BREAKER
TRIP UNIT
Rear Access Horizontal
Busbar connection
Remarks
Ratings
Standard
400-1600A
Standard
400-2000A
Standard
400-3200A
Standard
3200-5000A
Rear Access
(Horizontal)
Busbar connection
Remarks
Ratings
Cassette available (²)
400-1600A
Cassette available (1)
400-1600A or 2000A
400-2000A
Cassette available (1)
2500, 3200A or 4000A
Cassette available (1)
3200-5000A
Deutsch
Einschubträger verfügbar
Baugröße
Horizontal oder Vertikal
wahlweise
Leistungen
Rückseitiger, horizontaler Schienenanschluss
Rückseitiger, vertikaler Schienenanschluss
Rückseitiger, nur vertikaler Schienenanschluss
Standard
Der Baugröße 2 Einschubträger wird geliefert mit...
Bei vertikalem Gebrauch maximal Wert von..
LOCKS
ACCESSORIES
Tabelle 1.11: Anschlussart Festeinbau
Tabella 1.11: Opzioni di connessione per interruttore in esecuzione fissa
Rear Access Vertical
Busbar connection
Remarks
Ratings
Optional
400-1600A
Optional
400-2000A
Optional
400-3200A
Standard
4000A
Optional
3200-5000A
Standard
6400A
Tabelle 1.12: Anschlussart Ausfahrtechnik-Einbau
Tabella 1.12: Opzioni di connessione per interruttore in esecuzione estraibile
Rear Access Vertical only
Busbar connection
Remarks
Ratings
Cassette available (²)
400-1600A
Cassette available (1)
400-1600A & 2000A
400-2000A
Cassette available (1)
2500 & 3200A
Cassette available (1)
6400A
Italiano
Parte fissa disponibile
Taglia
Connessione sbarre ad accesso anteriore
orizzontale o verticale
Opzionale
Tipo interruttore aperto
Valori
Connessione sbarre orizzontali accesso posteriore
Connessione sbarre verticali accesso posteriore
Connessione sbarre SOLO verticali accesso posteriore
Osservazioni
Standard
La parte fissa in taglia 2 è fornita con:
Connessioni accesso posteriore connessione universale
Connessione sbarre accesso posteriore universale
Quando viene utilizzato in senso orizzontale ha un valore massimo
di:
Quando viene utilizzato in verticale ha:
TESTS
APPENDIX
Front Access
Busbar connection
Remarks
Ratings
Optional
400-1600A
Optional
400-1600A or 2000A
Optional
400-3200A or 4000A
Front Access
Busbar connection
Remarks
Ratings
Cassette available
400-1600A
400-1600A or 2000A
Cassette available
400-2000A
Cassette available
2500, 3200A or 4000A

Advertisement

loading