2.4

Technical data

Technical data
Number of Bus Terminals
Digital peripheral signals
Analog peripheral signals
Protocols
Configuration possibility
Maximum number of bytes
Bus connection
Power supply
Input current
Input inrush current
K-bus power supply up to
Power contact voltage
Power contact current load
Dielectric strength
Recommended fuse
Mounting [} 20]
Weight
Permissible ambient
temperature range during
operation
Permissible ambient
temperature range during
storage
Permissible relative humidity
Vibration / shock resistance
EMC immunity / emission
Installation position
Protection class
Approvals/markings
System data
Number of I/O modules
Data transfer medium
Max. cable length
Data transfer rates
Operation modes
DeviceNet type
Ex marking
Standard
Marking
ATEX
II 3 G Ex nA IIC T4 Gc
BK52x0 and LC5200
BK5200
BK5210
64
512 inputs/outputs 256 inputs/
outputs
256 inputs/outputs -
via the KS2000 configuration software or the controller (TwinCAT)
512 bytes of input
32 bytes of input
data, 512 bytes of
data, 32 bytes of
output data
output data
1 x open pluggable connector, 5-pin
24 V
(-15%/+20%), via bus cable 11 ... 25 V
DC
(according to DeviceNet specification)
70 mA + (total K-bus current)/4, 500 mA max.
approx. 2.5 x continuous current
1750 mA
500 mA
maximum 24 V
DC
maximum 10 A
500 V (power contact / supply voltage / Bus Coupler)
≤ 10 A
on 35 mm support rail according to EN 60715
app. 150 g
approx. 130 g
0 °C ... +55 °C
0 °C ... +55 °C
-25 °C ... +85 °C
-25 °C ... +85 °C -40 °C ... +85 °C -25 °C ... +85 °C
95 %, no condensation
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
variable
IP20
CE, cULus,
CE, cULus, GL,
ATEX [} 28]
ATEX [} 28]
DeviceNet BK5200, BK5210, BK5250, LC5200
64
shielded, twisted copper wire with energy supply, 5-pin
500 m
125 kbaud
Bit-Strobe, Polling, Cyclic, Change-of-State (COS)
Communications adapter
Version: 2.0.0
BK5250
64 (255 with K-
bus extension)
1,020 inputs/
outputs
256 inputs/
outputs
512 bytes of input
data, 512 bytes
of output data
1750 mA
approx. 100 g
-25 °C ... +60 °C
(ET)
CE, cULus,
ATEX [} 29]
250 m
250 kbaud
Product overview
LC5200
64
256 inputs/
outputs
-
32 bytes of input
data, 32 bytes of
output data
directly to spring-
loaded terminal
500 mA
approx. 100 g
0 °C ... +55 °C
CE, cULus,
ATEX [} 28]
100 m
500 kbaud