Air Flow Data -36K - Friedrich VRP12K Service And Parts Manual

Hide thumbs Also See for VRP12K:
Table of Contents

Advertisement

Air Flow Data -36k

Indoor CFM & External Static Pressure
Model
Air Flow Data
Indoor CFM
.15" ESP *
.20" ESP
.30" ESP - Max @ Low Speed
.40" ESP
.50" ESP - Max @ High Speed
* Rated at 0.15 " ESP, High and includes 0.08
Condenser CFM & External Static Pressure
VRP
is designed to mount through an exterior wall through a plenum (VRPXWP****) with an external louver (VRPXAL*).
®
Condenser External Static Pressure
VRP Model
VRP 36000 Btu
CAUTION: If the Friedrich designed plenum and louver combinations are not used, the louver/duct design must be evaluated to
insure the total pressure drop does not exceed the maximum allowable limits.
19
SPECIFICATIONS
Low
1015
875
750
565
440
" ESP for factory installed 1 "
Design
CFM
ESP ( " WC)
2030
0.03
Figure 206 (36K Air Flow Data)
VRP36K
High
1200
1160
1080
970
835
Maximum
ESP ( " WC)
0.20