Compressor checks

ELECTRIC SHOCK HAZARD
Disconnect power to the unit before
servicing. Failure to follow this warning
could result in serious injury or death.
Caution: After disconnecting power from unit, allow 2 minutes for capacitors to discharge before handling MCS board, disconnecting
leads, or taking readings with a meter.
1. Remove front panel from unit and gain access to the MCS board.
2. Locate and disconnect the motor winding leads shown in the figure below.
U= Red V= Blue W= Black
3. Using an OHM Meter, check resistance from U to V, U to W, and V to to W.
All of the readings should be within 0.1 ohms of each other.
A difference of more than 01. ohms indicates that windings may be damaged and the compressor should be replaced.
NOTE: Actual OHM values may vary due to temperature of the compressor.
4. Using a MegOhm Meter, check the motor windings for a short to ground.
Measure the resistance of each winding to ground.
A reading of less than 10 Megohms indicates that the motor windings may be damaged and the compressor should be
replaced.
Compressor
Leads U, V,
and W
126
COMPONENT TESTING
WARNING
Figure 604 (Compressor Checks)
WARNING
BURN HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with a torch.
Failure to follow these procedures could
result in moderate or serious injury.