Check the Outdoor Fan 12k/24k

Caution: Wait for 2 minutes after removing power from the unit to allow capacitors to discharge before handling the MCS board,
disconnecting leads or connectors, or taking ohm readings.
1. Remove outdoor fan connector from MCS board at J8 as shown in figure below.
2. Ohm out all three wires to each other.
3. 15 ohms is a normal reading.
4. If the resistance is not within 0.1 ohms, replace motor or repair associated wiring.
127
COMPONENT TESTING
Figure 605 (Outdoor Fan)
Outdoor Fan
Connector