TABLE OF CONTENTS INTRODUCTION‑ Part Load Performance‑ VRP® Variable Speed System vs. Fixed‑speed System‑ FreshAire™ Conditioned Fresh Air‑ Reheat Coil - Augments VRP’s Dehumidification Capability- Important Safety Information‑ Personal Injury Or Death Hazards‑ Model and Serial Number Identification Guides- SPECIFICATIONS‑ Cooling Performance‑...
Page 3
TABLE OF CONTENTS Wall Controller Installation 12 & 24k‑ Return Air Door Installation12 & 24k‑ FreshAire System Set‑up and Operation‑ Final Installation Checklist‑ TROUBLESHOOTING- VRP Troubleshooting Map‑ Required Tools‑ Required Skills‑ Troubleshooting by Rule Out Methodology‑ Diagnostic Codes‑ Check For Power‑ Diagnostic Code (Temperature Based)‑...
Page 4
12k E Models (Unit Assembly)‑ 12K E Models Basepan‑ 12K E Models (230v Electrical Controls)‑ 12K E Models (265v Electrical Controls)‑ Accessories‑ ACCESSORIES‑ Wall Controller/ Thermostat‑ Installation Accessories and Descriptions- ‑ APPENDIX Thermistor Values‑ CUSTOMER SATISFACTION and QUALITY ASSURANCE‑ FRIEDRICH AUTHORIZED PARTS DEPOTS‑...
In sum, The Friedrich VRP offers a significant value to all parties involved in the design and construction of a new building. Because of the simpler and more straightforward nature of the packaged design, and the ability t o potentially downsize or eliminate additional make up air and humidity control equipment, the VRP reduces much of the headache and complexity facing the design engineer.
INTRODUCTION Part Load Performance Exceptional Efficiencies with VRP®: Partial load conditions prevail for the majority of the time. VRP’s Precision Inverter® compressor can operate down to 40% of rated capacity or up to 120% matching the unit’s output to the actual demand of the space and, therefore, only consumes the energy that is required.
INTRODUCTION VRP® Variable Speed System vs. Fixed-speed System Low Ambient Heat Pump Performance: Variable speed technology enables VRP units to supply continuous hot air in heat pump mode even at low outdoor ambient temperatures. This reduces strip heat usage resulting in exceptional savings with VRP units when compared with Figure 103(Cost Savings) Precise Temperature &...
INTRODUCTION FreshAire™ Conditioned Fresh Air FreshAire is a dedicated fresh air system that brings in up to 70 CFM of outdoor air into the VRP® unit. The FreshAire system uses one fan (up to 35 CFM) or two fans (up to 70 CFM) (depending on outdoor air CFM volume requirements) to bring in fresh outside air into the the unit.
INTRODUCTION Reheat Coil - Augments VRP’s Dehumidification Capability Temperature differences are not the only source of discomfort in a living space. Humidity also plays a big role — especially in climates that tend to be both hot and humid. The air conditioning industry’s focus on humidity issues has elevated the importance of dehumidification.
INTRODUCTION Important Safety Information The information in this manual is intended for use by a qualified technician who is familiar with the safety procedures required for installation and repair, and who is equipped with the proper tools and test instruments required to service this product.
Page 11
DO NOT OPERATE EQUIPMENT DURING ACTIVE STAGES OF CONSTRUCTION To ensure proper operation, Friedrich requires that all equipment is not operated during active construction phases. This includes active stages of completing framing, drywalling, spackling, sanding, painting, flooring, and moulding in the equipment’s designated conditioning space.
INTRODUCTION Personal Injury Or Death Hazards WARNING AVERTISSEMENT ADVERTENCIA Do not remove, disable or Ne pas supprime, désactiver ou No eliminar, desactivar o pasar SAFETY bypass this unit’s safety contourner cette l´unité des por alto los dispositivos de devices. Doing so may cause dispositifs de sécurité, faire vous seguridad de la unidad.
INTRODUCTION Model and Serial Number Identification Guides Figure 107 (Model Identification Guide) 17 12 M 00001 YEAR OF MANUFACTURE NUMERIC SEQUENCE 17 = 2017 18 = 2018 FIRST UNIT OF EACH MONTH = 00001 19 = 2019 20 = 2020 21 = 2021 22 = 2022 MONTH OF MANUFACTURE 01 = JANUARY...
0.017 0.11 CAUTION: If the Friedrich designed plenum and louver combinations are not used, the louver/duct design must be evaluated to insure the total pressure drop does not exceed the maximum allowable limits. Figure 204 (12K and 24K Air Flow Data)
SPECIFICATIONS Dimensions 12k and 24k Unit Dimensional Data VRP Dimensional Data 12K DUCT FLANGE VRP Dimensional Data 24K Model VRP12K VRP12R VRP24K VRP24R Dimensions (W x D x H) 26 1/8" x 25 1/8" x 52" 26 1/8" x 25 1/8" x 62" Shipping Dimensions (W x D x H) 28 1/8"...
SPECIFICATIONS 12k and 24k Unit Installation Dimensional Data Typical Closet Closet Wall Plenum Access Panel VRP Chassis Louver and hinge (24k shown) Model VRP12K VRP12R VRP24K VRP24R Outside Wall- Cut Out Dimensions Dimensions (W x H) " x 32 " For VRPXWPA-8 or VRPXWPA-14 Plenum Dimensions (W x H) "...
28 3/4 in. 7 1/2 in. 7 1/2 in. 1 1/2 in. high " 6 3/4 in. • The use of a Friedrich wall 27 5/8 in. plenum is required for 19 in. installation. Refer to this 33 3/8 in. 32 in.
OPERATION Sequence Of Operations Cooling Sequence: The wall thermostat provides the temperature set point as well as the current dry bulb temperature and relative humidity. Upon a call for cooling, the compressor modulates based on the difference between room temperature and set point. As cooling demand decreases the compressor will modulate to a minimum speed.
OPERATION Component Identification Electric Heater • 2.5 / 3.4 / 5.0 / 7.5 / 10.0 Kilowatt variations • Located directly behind the indoor coil and in front of the indoor blower COMPONENT IDENTIFICATION-ELECTRIC HEATER FIGURE 308 (...
OPERATION Component Identification Electronic Expansion Valve • Three sizes • • • • Used to control superheat • Controlled by magnetic pulse COMPONENT IDENTIFICATION-ELECTRONIC EXPANSION VALVE FIGURE 309 (...
OPERATION Component Identification Compressor Control • The rate of change of the space conditions is assessed periodically and the compressor frequency is changed accordingly. • Unless diagnostically conflicted, the compressor will operate in some capacity any time there is a cooling or heat pump demand.
OPERATION Component Identification Reheat Control • The VRP models, when equipped with Evaporator Coil the reheat option, increase room dehumidification capability. • The reheat option has a coil installed Reheat Coil downstream of the main indoor evaporator coil. • When activated, a portion of the compressor discharge gas is routed through the reheat coil.
Please carefully read and follow the installation insrtructions and safety warnings detailed in this manual. All applicable na- tional and local mechanical and electrical codes should be followed and take precedence over any Friedrich requirements or reccomenedations regarding installation applications detailed in this manual.
72” must be kept. FENCE MAJOR OBSTRUCTIONS The the example pictured above is for reference only and does not represent all possible installations. Please contact Friedrich Air Conditioning for information regarding effects of other installation arrangements. INSTALLATION CLEARANCE FIGURE 401 (...
INSTALLATION Interior (Closet) Wall Opening Dimensions Interior(Closet) Wall Opening Dimensions 12 & 24k Return Air Access Door Wall Cut-Out 30” 69¾” NOTE: To maintain ease of removal and serviceability, if the unit is installed on a platform ensure that the total height of the unit from the floor does not exceed the height of the interior rough opening.
INSTALLATION Preliminary Plumbing Preliminary Plumbing Standard (Front Install) The image to the right shows the installation closet for the standard (Front Install) configuration (where the wall plenum is opposite the service access door). A drainage system is required, and should provide a “P-trap”...
INSTALLATION Wall Plenum Installation Wall Plenum Installation 12 & 24k Parts included in Plenum kit: Outside Plenum (Part A) Divider (Part C) Inside Plenum (Part B) Baffle (Part D) Field Supplied Parts: Sealant, attachment screws, and flashing Flashing are field supplied. Silicone sealant is recommended. Sealant VRPXWPA-8, VRPXWPB-8 adjust for walls up to 4”- 8”...
Page 47
INSTALLATION Wall Plenum Installation Wall Plenum Installation 12 & 24k Step 1 - Outside Wall Plenum Half Note: The wall plenum is not designed to carry any structural load. A load bearing header must be built above the rough opening. 1) Prepare the rough opening.
Page 48
INSTALLATION Wall Plenum Installation Wall Plenum Installation 12 & 24k Step 2 - Inside Wall Plenum Half Caulk all 8 Flange Corners and Unused Holes Detail A 1) Apply sealant to all 4 flange corners and unused holes. See Detail A. 2) Place the baffle (Part D) on the approprate baffle mounting tabs located on the inner perimeter of the inside plenum half based on unit size (Compact/Standard).
Page 49
INSTALLATION Wall Plenum Installation Wall Plenum Installation 12 & 24k Step 3 - Inside Wall Plenum (cont.) Detail B Note: Do not place any screws, fasteners, or penetrating holes through the top or bottom of the plenum assembly. 1) Drill pilot holes on the interior of the inside plenum half (Part B) as show in Detail B. Pilot holes should be located approxiamtely 4”...
INSTALLATION Installation of the louver PRIOR to Wall Plenum Installation Hold the louver up to the Outside Wall Plenum Part A and line up the louver top with the very top edge of the 3/4” flange. Line up Louver Installation the Wall Plenum holes with the threaded holes in the louver, install and tighten the 8 screws.
INSTALLATION Final Wall Plenum and Architectural Louver Installation Final Wall Plenum And Architectual Louver Installation Plenum Divider Extension Plate Installed Plenum Divider Extension Plate (Baffle) into Full Plenum Assembly Ensure that the weather strip is undamaged and provides a continuous seal around the inner perimeter of the plenum.
INSTALLATION Unit Installation Unit Installation Unit Placement Prior to Installation (Front-Install Configuration) All louver, plenum, rough plumbing, and rough wiring steps must be complete prior to final installation of the air conditioning chassis. (Unit Installation FIGURE 411...
INSTALLATION Final Unit Installation Overview Final Unit Installation Overview Unit Final Placement - Front Install Ensure that power if off at the junction box feeding power to the air conditioner until all process steps are completed. Move the unit from the shipping base and onto the installation site. Insert the unit’s rear extension into the wall plenum.
INSTALLATION Side Configuration Installation Side Configuration Installation Left Install VRP Unit Left Install VRP Unit Prepared for Installation in Closet (Fully Installed) For side-install applications, place the unit adjacent to the closet and slide it in. Then, slide the unit backwardward into the plenum.
INSTALLATION Final Drain Installation Unit Drain Installation Unit Drain Installation ” ” ” NOTE: Failure to follow the following procedures may result in serious property damage. A field supplied secondary condensate pan may be required. Check with local codes. In case of drainage system blockage, the unit base will allow excess water to flow out of the unit through the plenum and the architectural louver.
INSTALLATION Ductwork Installation Ductwork Installation Supply air duct connection is the responsibility of the installer and should be installed per industry best practices. Sheet metal or duct board may be used for the transition from the discharge to 10” or larger diameter flexible ducting.
INSTALLATION Wall Controller Installation 12 & 24k Wall Controller Installation Proper Wiring of VRP unit to Wall Controller Use shielded and stranded CAT 6 cable with twisted pairs to wire the wall controller. Use the wire colors with the corresponding terminals on the wall controller to the VRP unit as shown in the table below. Table shows which wire pairs go with which screw terminal.
Page 58
Wall Controller Installation INSTALLATION Wall Controller Installation 12 & 24k Electrical Installation Electrical Installation Remove and discard hole knock-out from the side of the unit (Detail A) Remove and discard hole knock-out from the side of the unit (Detail A) Remove the Electrical Access Panel (Detail B) to expose the Incoming Power Terminal Block (Detail C, see below)
Page 59
INSTALLATION Electrical Installation Electrical Installation Electrical Installation 12 & 24k Remove and discard hole knock-out from the side of the unit (Detail A) Remove and discard hole knock-out from the side of the unit (Detail A) Remove the Electrical Access Panel (Detail B) to Remove the electrical access panel to expose the incoming expose the Incoming Power Terminal Block Ppwer terminal block (Detail C, see below)
INSTALLATION Return Air Door Installation Return Air Door Installation12 & 24k Option 1 Option 2 The door panel is supported along one edge by the provided hinge. The opposite edge has a latch which secures the panel to the adjacent framed structure. The kit contains hinge bracket for mounting the door with the return air openings low (shown in option 1) or high (shown in Option 2) on the door.
INSTALLATION FreshAire™ System Set-Up and Operation FreshAire System Set-up and Operation FreshAire™ System Set-Up and Operation DETA IL If equipped with the FreshAire™ System, the unit will come with a FreshAire filter and blank-off plate. Detail A Remove the blank-off plate prior to turning the unit on. If equipped with the FreshAire™...
Authorized single (F option) outdoor air fan and filter, or dual Friedrich Warranty Service Company in the area (D option) outdoor air fans and filters. for future reference if necessary.
TROUBLESHOOTING Required Skills 1. Patience – Revolutionary digital communicating technology has replaced older analog components. 2. Patience – Needle point leads will save you time when backprobing molex connectors. 3. Patience – Know who to call when you need help. 4.
TROUBLESHOOTING Diagnostic Codes Diag Description Diagnostic Check point Solution Return Air sensor (T8) is open or shorted Indoor Coil Cool Inlet sensor (T1) is open or shorted Outdoor Coil Heat Inlet sensor 1. An open or shorted sensor is (T7) is open or shorted detected by the A/D conversion Discharge Air sensor (T9) value residing at the upper or lower...
Page 67
TROUBLESHOOTING Diagnostic Codes Diag Description Diagnostic Check point Solution 1. Ensure that the IDB is connected properly and is operational. 1. Lower than usual IDB speeds. 2. Check that there is no blockage in the The Indoor Coil at sensor T1’s location duct work.
Page 68
TROUBLESHOOTING Diagnostic Codes Diag Description Diagnostic Check point Solution 1. The Compressor has run at low frequency ( less than 35 Hz) for 200 con‑ Compressor Lubrication secutive minutes and requires lubrication 2. Monitors if the FMC has not provisioned Provisioned is defined as both switch and Unit Not Provisioned Replace with provisioned the FMC...
Page 69
TROUBLESHOOTING Diagnostic Codes Diag Description Diagnostic Check point Solution Compressor Start Failure Compressor speed synchronization issue "1. Check compressor wires for damage. for 10 consecutive seconds. 2. Verify connection of the compressor wires. 3. Replace motor board. 4. Replace compressor." Compressor Current Limiter The total compressor current exceeds a "This error should automatically correct...
TROUBLESHOOTING Check For Power 1. If the wall controller does not light up, ensure the unit has power. 2. Check the electrical circuit breaker. 3. Check the units disconnect. 4. Check power at L1 and L2.
TROUBLESHOOTING Diagnostic Code (Temperature Based) Temperature Based: Thermistors (sensors) modify VDC and is interpreted through the FMC. Errors indicate a possible issue with the sensor, FMC, or the sensor has detected an abnormal condition (or an out of parameter value). Solution: Sensor error, FMC error, or abnormal condition.
R-410A SEALED SYSTEM REPAIR The following is a list of important considerations when working with R‑410A equipment WARNING R‑410A pressure is approximately 60% higher than R‑22 pressure. Refrigeration system under high pressure 2. R‑410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.
R-410A SEALED SYSTEM REPAIR Refrigerant Charging WARNING RISK OF ELECTRIC SHOCK Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service. Failure to do so could result in electric shock, serious injury or death. WARNING Refrigeration system under high pressure service this equipment.
R-410A SEALED SYSTEM REPAIR Undercharged Refrigerant Systems An undercharged system will result in poor performance (low pressures, etc.) in both the heating and cooling cycle. Whenever you service a unit with an undercharge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit.
R-410A SEALED SYSTEM REPAIR Overcharged Refrigerant Systems Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confirm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated. Whenever an overcharged system is indicated, always make sure that the problem is not caused by air flow problems.
R-410A SEALED SYSTEM REPAIR Restricted Refrigerant System Troubleshooting a restricted refrigerant system can be difficult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions. A partial restriction allows some of the refrigerant to circulate through the system.
R-410A SEALED SYSTEM REPAIR Sealed System Method of Charging/ Repairs WARNING CAUTION BURN HAZARD FREEZE HAZARD Proper safety procedures must be followed, Proper safety procedures must be followed, and proper protective clothing must be worn and proper protective clothing must be worn when working with a torch.
R-410A SEALED SYSTEM REPAIR Compressor replacement 1. Be certain to perform all necessary electrical and refrigeration tests to be sure the compressor is actually defective before WARNING replacing. ELECTRIC SHOCK HAZARD Disconnect power to the unit before 2. Recover all refrigerant from the system though the process servicing.
R-410A SEALED SYSTEM REPAIR Compressor Replacement -Special Procedure in Case of Compressor Burnout 1. Recover all refrigerant and oil from the system. WARNING 2. Remove compressor,and EEV. 3. Flush evaporator, condenser and all connecting tubing with dry HIGH PRESSURE HAZARD nitrogen or equivalent.
R-410A SEALED SYSTEM REPAIR Replace The Reversing Valve WARNING HIGH PRESSURE HAZARD NOTICE Sealed Refrigeration System contains refrigerant and oil under high pressure. FIRE HAZARD Proper safety procedures must be followed, and proper protective clothing must be worn electically unsafe conditions which could cause moderate when working with refrigerants.
R-410A SEALED SYSTEM REPAIR Replace The Condensor Coil 12k/24k 1. Remove unit from the closet. 2. Ensure no charge is left in the system, evacuating according to EPA standards. 3. Remove the lower left panel. 4. Remove six mount screws on rear of condenser coil. 5.
R-410A SEALED SYSTEM REPAIR Replace The Evaporator Coil 12k/24k 1. Remove unit from closet. 2. Ensure no charge in the system, evacuating according to EPA standards. 3. Remove top panel. 4. Remove duct collar. 5. Remove left side upper panel. NOTE: The 24k units utilize 2 evaporator coils and 2 reheat coils if applicable.
R-410A SEALED SYSTEM REPAIR Replace The Evaporator Coil Drain Pan 1. Remove unit from the closet. 2. Remove top panel. 3. Remove filter. 4. Remove left and right upper side panels 5. Carefully lift coil up a few inches and support to avoid damage to tubing. 6.
COMPONENT TESTING Electronic Expansion Valve (EEV) WARNING WARNING BURN HAZARD CUT/SEVER HAZARD Proper safety procedures must be followed, Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc. and proper protective clothing must be worn when working with a torch. Failure to do so could result in serious injury.
COMPONENT TESTING Reversing Valve Description And Operation The Reversing Valve controls the direction of refrigerant flow to the indoor and outdoor coils. It consists of a pressure‑operated, main valve and a pilot valve actuated by a solenoid plunger. The solenoid is energized during the heating cycle only.
COMPONENT TESTING Testing The Reversing Valve Solenoid Coil WARNING ELECTRIC SHOCK HAZARD Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death. The solenoid coil is an electromagnetic type coil mounted on the reversing valve and is energized during the operation of the compressor in the heating cycle.
COMPONENT TESTING Checking The Reversing Valve WARNING HIGH PRESSURE HAZARD Sealed Refrigeration System contains refrigerant and oil under high pressure. Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants. Failure to follow these procedures could result in serious injury or death.
COMPONENT TESTING Testing The Reheat Valve Solenoid Coils Check the Reheat Valve: 1. Turn off high voltage electrical power to unit. 2. Disconnect yellow wire from Reheat Solenoid relay and red wire from L2 Terminal block. 3. Check for electrical continuity through the coil. If you do not have continuity replace the coil.
COMPONENT TESTING Touch Test Chart : To Service Reversing Valves NORMAL FUNCTION OF VALVE NOTES: VALVE OPERATING * TEMPERATURE OF VALVE BODY CONDITION ** WARMER THAN VALVE BODY POSSIBLE CAUSES CORRECTIONS Cool Normal Cooling Cool *TVB as (2) as (1) Cool Normal Heating Cool...
COMPONENT TESTING Compressor checks WARNING WARNING BURN HAZARD ELECTRIC SHOCK HAZARD Proper safety procedures must be followed, Disconnect power to the unit before and proper protective clothing must be worn servicing. Failure to follow this warning when working with a torch. could result in serious injury or death.
COMPONENT TESTING Check the Outdoor Fan 12k Caution: Wait for 2 minutes after removing power from the unit to allow capacitors to discharge before handling the Inverter Board, disconnecting leads or connectors, or taking ohm readings. 1. Remove Power from the Unit. 2.
COMPONENT TESTING Replace the Outdoor Fan 12k Caution: Wait for 2 minutes after removing power from the unit to allow capacitors to discharge before handling the MCS board, disconnecting leads or connectors, or taking ohm readings. 1. Remove unit from closet. 2.
COMPONENT TESTING Check the Indoor Fan 1. Check termnials at terminal block for secure connection/ broken terminals. 3. Check for 10 vdc at green and brown wires at white molex connector for indoor fan motor next fmc board. 4. If line voltage is present at terminal block, but 10vdc is not present at white connecor, indoor fan motor is bad. 5.
COMPONENT TESTING Replace the Indoor Fan 12k/24k 1. Remove unit from closet. 2. Unplug yellow and white molex connectors. Unlock connector by pulling down on red tab and squeezing connector. 3. Remove wires from clips back to fan 4. Remove duct collar by removing screws 5.
COMPONENT TESTING Replace the Heating Elements 1. Remove duct work as neccesary to gain access to top panel. 2. Remove top panel. 3. Disconnect input wires (2 places) 4. Remove Mounting screws (4 places). 5. Lift heater element assembly straight up and out of unit. Figure 612 (Heating Elements)
COMPONENTS TESTING Driver Board Pin out Figure 613 (Driver Board) 1. Check power in L1 and L2. 2. Communication to Rs‑485 board. 3. Power and signal out. 4. Compressor UVW out. 5. Remove power from the unit and allow two minutes for capacitors to discharge before attempting to take continuity readings.
COMPONENTS TESTING Driver Board Replacement 1. Remove power from the unit and wait 2 minutes for capacitor bleed off before removing leads or handling the Driver board. 2. Remove front panel. 3. Disconnect electrical connections and tag wires. 4. Remove 4 9/64 allen head bolts. 5.
COMPONENT TESTING Check RS-485 ConverterBoard 1. Check for 12vdc vdc coming in from power supply board. 2. Check for V+ and V‑ signals going to Driver Board. 12 VDC + In 12 VDC- In V- To driver Board V+ to Driver Board Figure 615 (RS-485 Board)
COMPONENTS TESTING FMC Board Replacement Note: When ordering the part, the model and serial number must be supplied for flashing of board. 1. Disconnect all electrical connections, tag and identify wires. 2. Carefully compress pcb standoffs and remove board. 3. Install new board. Figure 617 (FMC Board)
COMPONENTS TESTING Heater Board Pin Out 12VDC+ in 12 VDC- in L1 in Heater Reversing Valve Element L1 Out Reversing Valve L2 in L1 in L2 Heater L2 In Element Out Figure 618 (Heater Board) 1. Check for 12 vdc between VCC 1 and ground. 2.Check for line voltage at L1 and L2, reversing valve L1 and L2, 3.
COMPONENTS TESTING Heater Board Replacement 1. Ensure power is removed from the unit. 2. Disconnect all wires and identify. 3.Remove board by carefully compressing standoffs. 4. Install new board. Figure 619 (Heater Board)
COMPONENTS TESTING Thermistor Locations T8 (Return Air Sensor) The T8 (Return Air Sensor) is located behind the Air Filter. Figure 620 (Thermistor Locations)
COMPONENTS TESTING Thermistor Locations T1 (Evaporator Coil In Sensor) T5 (Evaporator Coil Out Sensor) To access the evaporator coil sensors remove the top panel and right side upper panel. The top sensor is T5 ( Evap. Coil Out) The lower sensor is T1 ( Evap. Coil In.) Figure 621 (Thermistor Locations)
COMPONENTS TESTING Thermistor Locations T9 (Discharge Air Sensor) The T9 discharge air sensor is located inside the blower housing. Figure 622 (Thermistor Locations)
COMPONENTS TESTING Thermistor Locations T2 (Liquid Heat) T6 (Liquid Cool) The T2 and T6 Sensors are located in the outdoor section attached to the EEV ( Electronic Expansion Valve). The pipe going into the bottom of the EEV is T2 (Liquid Heat). The one on the pipe leaving the side of the EEV is T6 (Liquid Cool).
COMPONENTS TESTING Thermistor Locations T10 (Outdoor Ambient Air Sensor) The T10 (Outdoor Ambient Air Sensor) is located in the outdoor section, mounted on the bottom of the indoor blower housing. Figure 624 (Thermistor Locations)
COMPONENTS TESTING Thermistor Locations T7 (Cond. Coil Sensor) T7 (Cond. Coil Sensor is attached to the outdoor coil on the right hand side. This sensor is attached to the coil roughly halfway down on one of the return bends. Figure 625 (Thermistor Locations)
COMPONENTS TESTING Thermistor Locations T3 (Comp. Suction). The T3 (Comp. Suction) is attached to the compressor suction line. Figure 627 (Thermistor Locations)
COMPONENTS TESTING Thermistor Part numbers VPH and VRP revision –A/B models used a sensor pack for the indoor and outdoor sensors. VRP revision –C and newer all use single sensors. THe Single sensors are compatible with the sensor pack. The sensor packs are no longer available and all VRP/VPH models will use the single sensors going forward. The part numbers for the individual sensors are listed here.
COMPONENTS TESTING Replace Transformer 1. Remove Unit from closet if unit has front install configuration. 2. Remove right side panel. 3. Remove 4 screws from transformer box. 4. Trace wiring back to fuse block located on the bottom of the control box. 5.
COMPONENTS TESTING Check High and Low Pressure Limit Switches 1. Ensure power is removed from the unit. 2. At fmc board disconnect the (J8) and(J7) wires. 3. The switches are wired together in series and if either switch is faulty you will get an error code 14. 4.
COMPONENTS TESTING Check Basepan Heater CONDENSER BASEPAN HEATER T-STAT 1. Remove power from unit. 2. Check fuses for continuity. Replace fuses as required. 3. Check Basepan inline TSTAT. Open On Rise (Normally Closed)Open Temperature: 50°F ± 5°F Close Temperature: 32°F ± 11°F Strip back heatshrink and check that switch is closed if below 32 degrees and open if above 50 degrees 4.
UPDATING VRP FIRMWARE FMC Manual Update Process - Remove SD Card from FMC load on a PC or Laptop NOTE: Ensure Power is OFF! You will need an SD Card Reader to complete this step...
UPDATING VRP FIRMWARE FMC Update Process – Unzip Files to Blank or Formatted SD Card “xx” will be replaced by two numbers, indicating the software version. Example: 3.2.0.55 – Version 55 Open FMC Zip Folder Select all Files Copy to your SD Card Drive...
UPDATING VRP FIRMWARE FMC Update Process – Verify Files on SD Card Drive FMC Update Process – Loading new Firmware Insert SD Card into FMC and apply power. The FMC Firmware load will confirm by showing three green downward cascading LEDs:...
PARTS CATALOG 12k E Models (Unit Assembly) Figure 901...
Page 123
PARTS CATALOG Figure 902 12k E Models (Refigeration Without Reheat) 34.1 33.1...
Page 124
PARTS CATALOG Figure 903 12k E Models (Refigeration With Reheat) 35 36 34.1 33.1...
Page 125
PARTS CATALOG 12k E Models (Blower Module) Figure 904...
Page 126
PARTS CATALOG 12k E Models (Outdoor Fan) Figure 905...
Page 127
PARTS CATALOG 12k Main Diagram E Models ITEM Manuf. ID PART PART DESCRIPTION USED ON MODEL NUMBER 100020 80083565 ASSY SOUND INSUL LEFT COND 12K PREPAINTED 080150 80080198 FLANGE DISCHARGE VPI PREPAINTED 080160 80080197 FLANGE DISCHARGE VPI PREPAINTED 010224 80083669 BRACKET FILTER HOLDER PREPAINTED 080130...
Page 128
PARTS CATALOG 12k Main Diagram E Models ITEM Manuf. ID PART PART DESCRIPTION USED ON MODEL NUMBER 030120‑02 25018305 REVERSING VALVE BODY 030230 25063605 REVERSING VALVE SOLENOID 230V COIL 030230 25063705 REVERSING VALVE SOLENOID 265V COIL 080030 80081308 ASSY INSUL REAR EVAP VRP PREPAINTED 080110 80081521...
Page 129
PARTS CATALOG Figure 906 12k E Model Fresh Air...
Page 130
PARTS CATALOG 12k E Model Fresh Air ITEM op-find PART PART DESCRIPTION USED ON MODEL NUMBER 100041 80083140 FRESH AIR FILTER MERV 8 6X6X1 FRESH AIR 050050 80083434 GASKET OUTDOOR AIR FILTER FRESH AIR 050010 80530100 ASSY FRESH AIR BOX VRP FRESH AIR 050030 80083490...
Page 131
PARTS CATALOG Figure 907 12K E Models Basepan Non- Illustrated Parts Heat Shield- aluminum Tape...
PARTS CATALOG 12k E Models Basepan ITEM op-find PART PART DESCRIPTION USED ON MODEL NUMBER 010030 80083672 BASEPAN VRP PREPAINTED 010273 80080144 HEATER TUBE SERVICE KIT VR‑BH‑K, VR‑BH‑R 010240 80080104 COND./SLINGER DRAIN PAN VR BH‑S 010272 80080260 DRAIN PAN SUMP LOOP VR‑BH‑K, VR‑BH‑R SLOTTED VRP12/24 010260...
PARTS CATALOG Figure 908 12K E Models (230v Electrical Controls) Non-Illustrated Parts SENSOR EVAP COIL OUT ORG SENSOR RETURN AIR TEMP WHT SENSOR EVAP COIL IN GRN SENSOR DISCHARGE AIR YEL SENSOR COMPRESSOR DISCHARGE BLK SENSOR COMPRESSOR SUCTION BLU SENSOR HEATING LIQUID BRW SENSOR COOLING LIQUID ORG SENSOR CONDENSER OUT PNK SENSOR AMBIENT RED...
Page 134
PART DESCRIPTION USED ON MODEL NUMBER 060010 80083814 CONTROL BOX 060171 80080227 HEATER BOARD STAND OFF 060070 63900141 PCBA, FRIEDRICH HEATER CONTROLLER (FHC) 060120 80083723 BLOCK TERM 3 POLES X 6QC TAB#2‑ 010279 80083438 FUSE HOLDER BASEPAN HEAT 010281 80060030 FUSE 3AB 1.0A, 400VDC, TIME DELAY...
PARTS CATALOG 12K E Models (265v Electrical Controls) Figure 909 Non-Illustrated Parts SENSOR EVAP COIL OUT ORG SENSOR RETURN AIR TEMP WHT SENSOR EVAP COIL IN GRN SENSOR DISCHARGE AIR YEL SENSOR COMPRESSOR DISCHARGE BLK SENSOR COMPRESSOR SUCTION BLU SENSOR HEATING LIQUID BRW SENSOR COOLING LIQUID ORG SENSOR CONDENSER OUT PNK SENSOR AMBIENT RED...
Page 136
USED ON MODEL NUMBER 060010 80083814 CONTROL BOX 060171 80080227 HEATER BOARD STAND OFF 060070 63900141 PCBA, FRIEDRICH HEATER CONTROLLER (FHC) 060120 80083723 BLOCK TERM 3 POLES X 6QC TAB#2‑ 010279 80083438 FUSE HOLDER (BASEPAN HEAT) BASEPAN HEAT 010281 80060030 FUSE 3AB 1.0A, 400VDC, TIME DELAY...
PARTS CATALOG Accessories ITEM PART NUMBER PART DESCRIPTION USED ON MODEL VRPXWPA‑8 Wall Plenum with VRPXALA for 4” to 8” thick wall VRP12 VRPXWPB‑8 Wall Plenum with VRPXALB for 4” to 8” thick wall VRP12, VRP24 VRPXWPA‑14 Wall Plenum for with VRPXALA for 8” to 14” thick VRP12 wall VRPXWPB‑14...
ACCESSORIES Wall Controller/ Thermostat VRP Wall Controller / Thermostat Options Friedrich offers two types of control options for VRP units: - Standard Wall Controller (Wired), VRPXWCT - Energy Management Wall Controller with an Occupancy Sensor - Wired, VRPXEMRT2 - Wireless, VRPXEMWRT2...
APPENDIX Thermistor Values RESISTANCE TEMP RESISTENCE (K Ohms) TOLERANCE % All thermistors in the VRP units CENTR have a 10k ohm Resistence at 77° F. 210.889 225.548 240.224 6.50 6.51 178.952 190.889 202.825 6.25 6.25 The chart below shows the value vs. 151.591 161.325 171.059...
Page 142
FRIEDRICH will repair or replace, at its option, any defective part without charge for the part. Replacement parts are warranted for the remainder of the original warranty period.
CUSTOMER SATISFACTION and QUALITY ASSURANCE Friedrich is a conscientious manufacturer, concerned about customer satisfaction, product quality, and controlling warranty costs. As an Authorized Service Provider you play a vital role in these areas. By adhering to the policies and procedures you provide us with vital information on each warranty repair you complete. This information is used to identify product failure trends, initiate corrective action, and improve product quality, thereby further reducing warranty expenses while increasing customer satisfaction levels.
Need help?
Do you have a question about the VRP Series and is the answer not in the manual?
Questions and answers