Replace The Reversing Valve - Friedrich VRP12K Service And Parts Manual

Hide thumbs Also See for VRP12K:
Table of Contents

Advertisement

R-410A SEALED SYSTEM REPAIR

Replace The Reversing Valve

WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant
and oil under high pressure.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow these procedures could
result in serious injury or death.
1.
Recover refrigerant from sealed system. PROPER HANDLING OF RECOVERED REFRIGERANT ACCORDING TO EPA
REGULATIONS IS REQUIRED.
2.
Remove solenoid coil from reversing valve. If coil is to be reused, protect from heat while changing valve.
3.
Unbraze all lines from reversing valve.
4.
Clean all excess braze from all tubing so that they will slip into fittings on new valve.
5.
Remove solenoid coil from new valve.
6.
Protect new valve body from heat while brazing with plastic heat sink (Thermo Trap) or wrap valve body with wet
rag.
7.
Fit all lines into new valve and braze lines into new valve.
8.
Pressurize sealed system with a combination of R‑410A and nitrogen and check for leaks, using a suitable leak
detector. Recover refrigerant per EPA guidelines.
9.
Once the sealed system is leak free, install solenoid coil on new valve and charge the sealed system by weighing in
the proper amount and type of refrigerant as shown on rating plate. Crimp the process tubes and solder the ends shut.
Do not leave Schrader or piercing valves in the sealed system.
NOTE: When brazing a reversing valve into the system, it is of extreme importance that the temperature of the valve does
not exceed 250°F at any time.
Wrap the reversing valve with a large rag saturated with water. "Re‑wet" the rag and thoroughly cool the valve after
each brazing operation of the four joints involved.
The wet rag around the reversing valve will eliminate conduction of heat to the valve body when brazing the line
connection.
112
electically unsafe conditions which could cause moderate
or serious property damage.
Read, understand and follow the above warning.
WARNING
EXPLOSION HAZARD
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and
wear protective safety clothing etc.
Failure to follow proper safety procedures
could result in serious injury or death.
NOTICE
FIRE HAZARD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrp12rVrp24kVrp24rVrp36k

Table of Contents