Air Flow Data - Friedrich VERT-I-PAK VHA09K Installation & Operation Manual

Single package heat pump
Hide thumbs Also See for VERT-I-PAK VHA09K:
Table of Contents

Advertisement

Air Flow Data

Indoor CFM & External Static Pressure
MODEL
Fan Speed
ESP (")
0.0"
0.05"
0.10"
0.15"
0.20"
0.25"
0.30"
0.35"
0.40"
*Maximum Allowable Static. Units rated at 0.3" ESP.
Indoor airflow may be determined by measuring the external static pressure (ESP) of the duct system using an inclined
manometer or magnahelic gauge and consulting the above chart to derive actual air flow. Under no circumstances should
the Vert-I-Pak be operated at an higher external static pressure than indicated above. Operation of the Vert-I-Pak over the
recommended ESP will result in inadequate airflow, leading to poor performance and/or premature component failure.
Blower Control
All Vert-I-Paks, by default, will be configured to low speed blower operation. The speed setting can be changed to high speed by updating
the speed tap settings on the fan control relay. The blower fan speed setting cannot be changed at the thermostat. Regardless of wiring
GH and/or GL, the unit will continue to operate at the speed setting at the fan control relay.
Note: Any non-Friedrich thermostat or low voltage device being powered by the Vert-I-Pak will need to be reviewed and approved for use.
VHA09
Low
High
Low
360
420
360
340
400
340
325
385
325
310
370
310
295
355
295
270
325
270
*
*
260
300
260
*
--
--
--
--
--
--
VHA12
VHA18
High
Low
SCFM
460
620
450
580
430
550
415
510
400
480
380
450
350
400
*
*
--
365
--
320
VHA24
High
Low
High
705
675
765
675
635
735
640
600
700
610
560
670
585
525
635
565
490
615
550
440
600
*
500
400
540
450
350
490
*
*
9