Profinet System Variables; Profinet System Variables (Profinet Controller Functionality) - Phoenix Contact AXC F 1152 Installing, Starting Up, And Operating

Hide thumbs Also See for AXC F 1152:
Table of Contents

Advertisement

AXC F X152
Table 8-11

PROFINET system variables (PROFINET controller functionality)

System variable
PNIO_SYSTEM_BF
PNIO_SYSTEM_SF
PNIO_MAINTENANCE_DEMANDED
PNIO_MAINTENANCE_REQUIRED
PNIO_FORCE_FAILSAFE
PNIO_CONFIG_STATUS
PNIO_CONFIG_STATUS_READY
76 / 112
PHOENIX CONTACT
8.12

PROFINET system variables

Table 8-11
lists the PROFINET system variables of the integrated PROFINET controller
functionality.
Type
BOOL
BOOL
BOOL
BOOL
BOOL
WORD
BOOL
Description
No connection to a configured PROFINET device
An error has occurred in the PROFINET network, i.e., a con-
nection could not be established to at least one configured
PROFINET device. This value is not set if the "Control BF" pa-
rameter was set to FALSE for a PROFINET device. The
PROFINET device has therefore been excluded from con-
nection monitoring.
Diagnostic alarm on a configured PROFINET device
At least one PROFINET device is indicating a system error
(diagnostic alarm or maintenance alarm). The error priority
can be determined from the PNIO_DIAG_AVAILABLE,
PNIO_MAINTENANCE_DEMANDED, and PNIO_MAINTE-
NANCE_REQUIRED variables.
Maintenance demand
At least one PROFINET device is indicating the "maintenance
demand" alarm (high-priority maintenance alarm) with an ac-
tive connection. The PROFINET device can be identified
using the RALRM diagnostic block.
Maintenance required
At least one PROFINET device is indicating the "maintenance
requirement" alarm (low-priority maintenance alarm) with an
active connection. The PROFINET device can be identified
using the RALRM diagnostic block.
All PROFINET devices are prompted to set their configured
substitute values.
If required, the system variable can be written/set from the
program.
Configuration status of the PROFINET controller
This variable is set if the PROFINET controller has been ini-
tialized correctly. No desired configuration has been loaded
by PLCnext Engineer yet.