Figure 54: Setting the EOL Terminations on the Allure Series sensor Subnetwork Data Bus for the ECB/
ECL-600
Controller Series:
· ECB-600
· ECL-600
For ECB-600 / ECL-600, set the
Subnetwork EOL to ON
If an ECx-4XX Series I/O Extension Module is used with both a Cat 5e room device and an
ECB/ECL-600 controller, see
terminations.

Setting the Subnet ID Addressing for Room Devices

Each type of room device connected to a controller's Subnet Port must be set to a unique sub-
net ID address. The permitted subnet ID addressing range according to controller model is
shown in
Table
the table below.
Table 19: Subnetwork Module Compatibility and Maximum Supported Quantity Chart
Room Device Type
Allure EC-Smart-Vue
series
Allure EC-Smart-Comfort
series
Allure EC-Smart-Air
series
EC-Multi-Sensor series
84
Inside
ECB/ECL-600
EOL OFF
EOL ON
2-Wire Subnetwork Data Bus
16. The method to use to set a room device's subnet ID address is shown in
Configuration Method
Configured in an on-screen menu.
Dip Switch located next to the RJ-
45 subnet connectors
Rotary selector located next to
the RJ-45 subnet connector
Cat 5e Cable Subnetwork Bus
EOL set to ON
at the last
sensor at the
end of the Bus
on page 92 for how to set the EOL
See
Setting the Allure EC-Smart-Vue
Sensor's Subnet ID
page 98.
Setting the Allure EC-Smart-Air
and EC-Smart-Comfort Commu-
nicating Sensor Series' Subnet ID
Address
Setting the EC-Multi-Sensor
Series' Subnet ID Address
page 88.
Back of Allure
EC-Smart-Vue
ON
OFF
Addresson
on page 86
on
Network Guide