8 •
750-560 [2 AO 0-10V DC 10Bit 10mA 24V]

Display Elements

Any configuration of the output modules is possible when designing the
fieldbus node. Grouping of module types is not necessary.
The system supply and the field side supply voltage is used for the power
supply of the module.
The field side supply voltage of 0 V and 24 V to downstream I/O modules is
derived from adjacent I/O modules or from a supply module. The supply
voltage for the field side is made automatically through the individual I/O
modules by means of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The analog output module 750-560 can be used with all couplers/controllers
of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, -
323, -324 and -327).
2.1.1.3
Display Elements
13 14
A
A
B
B
Fig. 2.1.1-2: Display
elements
g056002x
LED
Channel
A
green
1
B
red
C
C
D
D
C
green
2
D
red
Designation
State Function
No operational readiness or the
off
internal data bus
communication is interrupted
Function
AO 1
Operational readiness and
on
trouble-free internal data bus
communication
off
Normal operation
Error
Short circuit to ground or
AO 1
on
overload ≥ 15 mA
No operational readiness or the
off
internal data bus
communication is interrupted
Function
AO 2
Operational readiness and
on
trouble-free internal data bus
communication
off
Normal operation
Error
Short circuit to ground or
AO 2
on
overload ≥ 15 mA
WAGO-I/O-SYSTEM 750