Process Image; Standard Format - WAGO 750 Manual

Fieldbus independent i/o modules
Table of Contents

Advertisement

2.1.1.6

Process Image

The analog output module 750-560 transmits 16-bit data and 8 status bits per
channel.
The digitalized output value is transmitted in a data word (16 bits) as output
byte 0 (low) and output byte 1 (high) via the process image of the coupler /
controller. This value is represented on bit B0 ... B14.
Some fieldbus systems can process the status information using by means of a
status byte.
In case of short circuit or overload, the returned status byte of this output
module is 0x40.
2.1.1.6.1

Standard Format

For the standard module 750-560, the numerical values ranging from 0x0000
to 0x7FFF are scaled on the output voltage ranging from 0 V to 10 V with a
resolution of 10 bit and an increment of 0.0098 V.
WAGO-I/O-SYSTEM 750
I/O Modules
Process values of module 750-560
Output
value
0 V ... 10 V
output value
0.00
<'0000.0000.0000.0000'
0.00
'0000.0000.0000.0000'
1.25
'0000.1111.1111.1111'
2.50
'0001.1111.1111.1111'
3.75
'0010.1111.1111.1111'
5.00
'0011.1111.1111.1111'
6.25
'0100.1111.1111.1111'
7.50
'0101.1111.1111.1111'
8.75
'0110.1111.1111.1111'
10.00
'0111.1111.1111.1111'
Short circuit or overload
750-560 [2 AO 0-10V DC 10Bit 10mA 24V]
numerical value
binary
hex.
<0x0000
0x0000
0x0FFF
0x1FFF
0x2FFF
0x3FFF
0x4FFF
0x5FFF
0x6FFF
0x7FFF
Process Image
status-
LED
byte
Error
dez.
hex.
AO 1, 2
<0
0x00
off
0
0x00
off
4095
0x00
off
8191
0x00
off
12287
0x00
off
16383
0x00
off
20479
0x00
off
24575
0x00
off
28671
0x00
off
32767
0x00
off
0x40
on
• 11