the previous Setpoint screen to the Modulation Screen (Figure 17). This screen
provides access to the PID (Proportional, Integral and Derivative) of the control.
The sola password is also required to change these parameters.
FIGURE 17 - CENTRAL HEAT CONFIGURATION - MODULATION SCREEN
 Changing High Limit Setpoint and Verifying Change
From the Status Summary Screen press Confi gure, then High Limits; this screen
will be used to set and/or test the Outlet High Limit Setpoint (Figure 18). The
sola password must be entered. By touching the Setpoint next to Outlet High
Limit Setpoint you can adjust the temperature up and down for the Setpoint you
desire or lower it for testing purposes. This change will require Verifi cation. Verify
as follows:
FIGURE 18 - HIGH LIMITS SCREEN
1. Arrow back to the Confi guration Menu and press Verify down in the lower
right hand corner. Figure 19.