SECTION 5
EDR-PURE-IOM-210617
NOTE:
TO BE COMPLETED BY A FACTORY AUTHORIZED TECHNICIAN HOLDING A VALID EDR CERTIFICATE OF REGISTRATION.
DATE
TECHNICIAN
TECH. COMPANY
ANNUAL MAINTENANCE:
Burner head removed and visually inspected
Burner head cleaned (30-72.5 psi air only)
Burner head reinstalled with new gaskets
Burner flange hardware torqued to spec (see Section 4 of IOM)
Low water probe(s) removed, cleaned, and reinstalled
Combustion air inlet filter replaced with new
Direct spark ignition replaced with new and gap properly set
Special gas vent system and condensate drains inspected
Combustion air intake system inspected
Safety relief valve tested, replaced if it does not fully reseat
Open factory Service Bulletin(s) addressed (where applicable)
Safety checks table completed
Combustion verification completed, adjust as necessary
WATER CHEMISTRY: Verify water chemistry is within specified limits, correct where required
pH (8.5-10.5)
Oxygen (<250 ppb)
Iron/Copper (<5 ppm)
Chloride (<200 ppm)
Hardness (<60 ppm)
Gylcol %
SAFETY CHECKS: Check all safeties below for proper operation and doc
DEVICE
Low Water Safety
Air Switch
Low Gas Pressure Switch
High Gas Pressure Switch
High Condensate Safety
Blocked Flue Switch
Tender No. MET21-117
Questions? Please Contact Your Local Manufacturer's Representative
SETTING
OPERATIONAL
Design & Build RFP: Gas Heating Upgrade
Replacement in Dartmouth
SERVICE DOCUMENTS
ANNUAL MAINTENANCE CHECKLIST
TECH CERTIFICATE #
BOILER MODEL
BOILER NB/SERIAL #
ument the final settings.
DEVICE
High Temperature Limit
Temperature Controller
Fuel Train Leak Test
Blower Leak Test
Addendum #5 Page 96 of 105
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
COMPLETE
(fill in tables below)
(fill in tables on reserve side)
ppb
ppm
ppm
ppm
%
SETTING
OPERATIONAL