Endura PURE Control™ Menu Screen Functions
ƒ Boiler Control
General individual boiler and ancillary functionality is accessed through this
category.
` BOILER STATUS
The screen shown below summarizes information and sensor status for the
boiler.
` SAFETY DEVICE STATUS
Devices will either have a green circle to the left indicating closed circuit or a red
circle indicating the device is open. The device indicated as the "open limit" is the
first device in the safety circuit open and should be the first device addressed
during troubleshooting.
Once the boiler is full of water, the following test of low-water cutoff can be ac-
complished:
1. Navigate to and tap the Test Low Water button on the screen.
2. Reset the Low Water condition by tapping the Reset Low Water button.
3. Perform appropriate test for any secondary Low Water controls.
` OPERATOR CONTROL
This screen is used for multiple functions: Start/Stop Deviations, Anti-Cycle
Timer, and Manual Burner Control.
The start and stop deviations instruct the burner when to enable and disable
around the setpoint temperature. Increasing the range will reduce cycling but
may result in larger temperature fluctuations.
When in Automatic Control, the temperature controller will modulate the
burner to a firing rate necessary to achieve the setpoint. To enter Manual
Control, tap the "Automatic Control" button, and it will change to "Manual
Control. " Enter a "Manual Firing Rate" in the box, and press OK to confirm.
When finished with maintenance, return to this screen and place the boiler
back into Automatic Control.
The Anti-Cycle Timer, if used, will prevent the burner from firing for a minimum
amount of time between cycles
Design & Build RFP: Gas Heating Upgrade
Replacement in Dartmouth
SECTION 3
EDR-PURE-IOM-210617
Addendum #5 Page 67 of 105