Changing/Testing SOLA High Limit Setpoint

Perform the following to change the High Limit Setpoint and verify the change:
1. From the Status Summary Screen press Con gure then scroll down to and
press High Limits, this screen will be used to set and/or test the Outlet High
Limit Setpoint. See Figure 26.
2. Enter the SOLA password by pressing the padlock icon and typing sola.
3. By touching the Setpoint next to Outlet High Limit Setpoint, you can adjust
the temperature up and down for the Setpoint you desire or lower it for
testing purposes. A change will require Veri cation (see below).
FIGURE 26 HIGH LIMIT SETPOINT

Verifying Changes to High Limit Setpoint

4. Arrow back to the con guration menu and press Verify in the lower right
hand corner. See Figure 27.
FIGURE 27 HIGH LIMIT SETPOINT
5. Press the Padlock in the upper right hand corner and enter the password
sola (if not already unlocked) then press Begin down in the lower right
hand corner. See Figure 28.
6. The parameters that you changed will appear, verify the change you made
is correct. Then press Yes. See Figure 29.
7. If there are no more changes the control will ask you for a reset. This can
SECTION 3
PHW-IOM-2013-0214