Prince Antec Controls Retrofit Manual page 34

Venturi valve
Table of Contents

Advertisement

33 | VVR– Manual | AntecControls.com
STEP 4
Select the valve you would like to calibrate. Configure the airflow device and actuator in the
PACE MANAGER screen.
STEP 5
Enter the balancing menu underneath the Airflow tab.
STEP 6
With the valve in the minimum airflow position (2VDC to actuator), loosen the ½" nuts
around the swivel nut and fasten it to the control arm on of the valve. Secure the swivel nut
with 7/16" wrenches. Ensure that the minimum flow matches the minimum position in the
balancing menu.
NOTES:
• Shifting the position nut towards the crank arm will decrease the flow of the valve.
• Shifting the position nuts away from the crank arm will increase the flow of the valve.
Small changes of position nuts have small effect on the minimum flow but larger effect
on the maximum flow.