Prince Antec Controls Retrofit Manual page 31

Venturi valve
Table of Contents

Advertisement

30 | VVR– Manual | AntecControls.com
STEP 6
After a module is found, confirm the Module Type is shown as LMX.
STEP 7
Select whether the valve has One POT Curve or Two POT Curves.
STEP 8
Select the operating range of the valve.
NOTES:
• Low pressure valves have a pressure range of 0.3 to 3.0 in.w.c
• Medium pressure valves have a pressure range of 0.6 to 3.0 in.w.c.
STEP 9
Enter the 8 airflow and voltage values for the original POT curve.
NOTE:
This information should come from the previous manufacturer. If this is not
available, please skip to
Creating a New POT
STEP 10
Enter the excitation voltage that was used to originally create the POT curve.
STEP 11
Review your entry and once satisfied click the Flash Module button.
A pop-up will display informing the result of the flash.
VVR - MANUAL
Curve.
CAUTION
Different manufacturers use different
excitation voltages for their controls. It is
recommended that before removing the
old controls, the excitation voltage is
verified with a physical measurement.