CALIBRATING THE RETROFIT

Calibration is the process of adjusting the valve's linkage assembly to ensure that the minimum position of the actuator
provides the minimum airflow of the valve, and the maximum position of the actuator provides the maximum airflow of the
valve.

Calibrating the VVR when using PACE

32 | VVR– Manual | AntecControls.com
STEP 1
Ensure that there is power to the PACE and that the flow potentiometer has been wired into
the controller.
NOTE:
If the POT curve is available, ensure it is configured before making any further
adjustments.
STEP 2
Connect a computer to PACE by using either the Keystone Jack (CKJ) or by connecting
directly to PACE.
NOTE:
For more information on connecting to PACE please refer to the Toolbox
manual.
STEP 3
Open Antec Toolbox and navigate to the PACE section of the software. Ensure a connected
status appears and that the valve(s) populate.