Original Curve
After Scaling
24 | VVR– Manual | AntecControls.com
STEP 8
The edit airflow menu will appear as zeros for all airflow and voltage values. Enter the 8
airflow and voltage values for the original POT curve.
This information should come from the previous manufacturer. If this is not
NOTE:
available, please skip to
Creating a New POT
STEP 9
Enter the excitation voltage that was used to originally create the POT curve. Then
select scale. This will edit the POT curve to the 3.3 volt excitation that PACE uses.
VVR - MANUAL
Curve.
CAUTION
Different manufacturers use different
excitation voltages for their controls. It is
recommended that before removing the
old controls, the excitation voltage is
verified with a physical measurement
.