Configuring a POT Curve for FHC

26 | VVR– Manual | AntecControls.com
STEP 1
Ensure the unit has power.
NOTE:
Please see the FHC Manual for power requirements
STEP 2
Using the Ethernet cable described in the
NET OUT port on the FHC and wire the 3-wire connection to the BCT using the
following wiring:
BCT Terminal
Wire Colour (PIN)
MS/TP COM
Brown (PIN 8)
MS/TP A+
Orange/White (PIN 1)
MS/TP B-
Orange (PIN 2)
STEP 3
Connect the BCT to the laptop using the USB-A to USB-B cable.
STEP 4
Open the Field Flash program.
VVR - MANUAL
Required
Tools, connect the RJ45 end to the
CAUTION
If experiencing connection issue to the
FHC, unplug any unneeded USB devices
and disconnect any Bluetooth devices
from the computer before starting the
program.