27 | VVR– Manual | AntecControls.com
STEP 5
The program will automatically detect a COM port that is communicating with the FHC.
If a COM port is not automatically detected, use the Scan COMs button to scan again.
If connection is still not detected, please proceed to the
manual.
STEP 6
After a module is found, confirm the Module Type is shown as FHC.
STEP 7
Select whether the valve has One POT Curve or Two POT Curves.
STEP 8
Select the operating range of the valve.
NOTES:
• Low pressure valves have a pressure range of 0.3 to 3.0 in.w.c
• Medium pressure valves have a pressure range of 0.6 to 3.0 in.w.c
STEP 9
Enter the 8 airflow and voltage values for the original POT curve.
This information should come from the previous manufacturer. If this is not
NOTE:
available, please skip to
Creating a New POT
STEP 10
Enter the excitation voltage that was used to originally create the POT curve.
VVR - MANUAL
Troubleshooting
section of the
Curve.
CAUTION
Different manufacturers use different
excitation voltages for their controls. It is
recommended that before removing the
old controls, the excitation voltage is
verified with a physical measurement.