Flash Messages - GE Multilin 350 Series Instruction Manual

Feeder protection system
Hide thumbs Also See for Multilin 350 Series:
Table of Contents

Advertisement

FRONT CONTROL PANEL INTERFACE

3.1.5.3 Flash messages

3–8
Courtesy of NationalSwitchgear.com
Table 1: Minor Self-test Errors
Self-test Error
Latched
Description of
Message
Target
Problem
Message?
MAINTENANCE
No
A bad IRIG-B input
ALERT: IRIG-B
signal has been
Failure
detected.
MAINTENANCE
No
Clock time is the
ALERT: Clock
same as the default
Not Set
time.
MAINTENANCE
No
Communication
ALERT: Comm
error between CPU
Alert 1, 2, or 3
and Comms board.
MAINTENANCE
No
Communication
ALERT :
error between 350
Ethernet Link
and Network.
Fail
Table 2: Major Self-test Errors
Self-test Error
Latched
Description of
Message
Target
Problem
Message?
UNIT FAILURE:
Yes
This warning is
caused by a unit
Contact
hardware failure.
Factory
Failure code (XXXX) is
(XXXX)
shown.
RELAY NOT
No
PRODUCT SETUP
READY: Check
INSTALLATION
Settings
setting indicates that
relay is not in a
programmed state.
Flash messages are warning, error, or general information messages displayed in response
to pressing certain keys. The factory default flash message time is 4 seconds.
Figure 3-6: Typical Flash message
S3 PHASE IOC
BLOCK 1
Logic Element 8
<SETPOINT STORED>
SETPOINT STORED
This flash message is displayed in response to the ENTER key while on any setpoint
message (see example above). The edited value was stored as entered.
COMMAND EXECUTED
This flash message is displayed in response to executing a command: ON, OFF, YES, NO,
etc.
CHAPTER 3: INTERFACES
How Often the Test
What to do
is Performed
Every 5 seconds
Ensure IRIG-B cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), ensure
IRIG-B receiver is
functioning, and check
input signal level (it may
be less than specification).
If none of these apply,
contact the factory.
Every 5 seconds
Set the date and time in
PRODUCT SETUP.
Every 5 seconds
If alert doesn't self-reset,
then contact factory.
Otherwise monitor
reccurences as errors are
detected and self-reset.
Detected
Check Ethernet cable and
instantaneously
Ethernet connection.
Check health of the
network. Check status of
external routers and
switches.
How Often the Test
What to do
is Performed
Every 5 seconds
Contact the factory and
provide the failure code.
On power up and
Program all required
whenever the
settings then set the
PRODUCT SETUP
PRODUCT SETUP
INSTALLATION
INSTALLATION setting to
setting is altered.
"Programmed".
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL