Flash Messages - GE 350-A9 Quick Start Manual

Feeder protection system feeder protection and control
Hide thumbs Also See for 350-A9:
Table of Contents

Advertisement

FRONT CONTROL PANEL INTERFACE

Flash messages

70
Self-test Error
Latched
Message
Target
Message?
MAINTENANCE
No
ALERT: High
Ambient
Temperature
MAINTENANCE
No
ALERT:
Daughter Error
MAINTENANCE
No
ALERT: Comms
Serial Invalid
* Failure is logged after the detection of 5 consecutive failures - that is after 25 seconds
Table 3-2: Major Self-test Errors
Self-test Error
Latched
Message
Target
Message?
UNIT FAILURE:
Yes
Contact
Factory (XXXX)
RELAY NOT
No
READY: Check
Settings
* Failure is logged after the detection of 5 consecutive failures - that is after 25 seconds
Flash messages are warning, error, or general information messages displayed in response
to pressing certain keys. The factory default flash message time is 4 seconds.
Figure 3-7: Typical Flash message
SETPOINT STORED
This flash message is displayed in response to the ENTER key while on any setpoint
message (see example above). The edited value was stored as entered.
COMMAND EXECUTED
This flash message is displayed in response to executing a command: ON, OFF, YES, NO,
etc.
INVALID PASSWORD
This flash message appears upon an attempt to enter an incorrect password, as part of
password security.
AR IN PROGRESS
This flash message appears when the Autoreclosure is in progress performing the
configured sequence.
Description of
How Often the Test
Problem
is Performed
The ambient
Every 1 hour
temperature is
o
above 80
C.
The rear
Every 5 seconds*
Communications
daughter board type
does not match the
order code.
The internal
Every 5 seconds*
communications
board does not
match the order
code.
Description of
How Often the Test
Problem
is Performed
This warning is
Every 5 seconds*
caused by a unit
hardware failure.
Failure code (XXXX) is
shown.
PRODUCT SETUP
On power up and
INSTALLATION
whenever the
setting indicates that
PRODUCT SETUP
relay is not in a
INSTALLATION
programmed state.
setting is altered.
350 FEEDER PROTECTION SYSTEM – QUICKSTART GUIDE
CHAPTER 3: INTERFACES
What to do
Increase ventilation to the
surroundings.
Replace the rear
communications
daughter board with the
correct board.
Contact factory.
What to do
Contact the factory and
provide the failure code.
Program all required
settings then set the
PRODUCT SETUP
INSTALLATION setting to
"Programmed".

Hide quick links: