Advanced Enervista Sr3 Setup Features; Flexcurve Editor - GE Multilin 350 Series Instruction Manual

Feeder protection system
Hide thumbs Also See for Multilin 350 Series:
Table of Contents

Advertisement

CHAPTER 3: INTERFACES

3.2.6 Advanced EnerVista SR3 Setup features

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
After successfully updating the 350 firmware, the relay will not be in service and will
require setpoint programming. To communicate with the relay, the communication
settings may have to be manually reprogrammed.
When communications is established, the saved setpoints must be reloaded back into the
relay. See Loading Setpoints from a File - section 3.2.4.11, for details.
Modbus addresses assigned to firmware modules, features, settings, and corresponding
data items (i.e. default values, min/max values, data type, and item size) may change
slightly from version to version of firmware.
The addresses are rearranged when new features are added or existing features are
enhanced or modified.

3.2.6.1 Flexcurve editor

The FlexCurve Editor is designed to allow the user to graphically view and edit the
FlexCurve. The Flexcurve Editor screen is shown below:
The Operate Curves are displayed, which can be edited by dragging the tips of the
curves
SOFTWARE SETUP
3–27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents