CHAPTER 6: SETPOINTS

6.3 S2 System Setup

S2 SYSTEM SETUP

CURRENT SENSING

POWER SYSTEM
BREAKER SETUP
USER CURVE
FLEXCURVE A
FLEXCURVE B
898781.cdr
6.3.1 Current sensing
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
S2 USER CURVE
PATH:
SETPOINTS > S2 SYSTEM SETUP > CURRENT SENSING
PHASE CT PRIMARY
Range: 1 A to 6000 A
Default: 500 A
Enter the primary rating of the three-phase feeder CTs wired to the relay phase CT
terminals (see above). For correct operation, the relay CT tap must match the feeder CT
tap (5 A or 1 A).
As the phase CTs are connected in wye (star), the calculated phasor sum of the three
phase currents (Ia + Ib + Ic = Neutral Current = 3I
overcurrent. In addition, a zero-sequence (core balance) CT which senses current in all of
the circuit primary conductors, or a CT in a neutral grounding conductor may also be
used.