GE Multilin 350 Series Instruction Manual page 127

Feeder protection system
Hide thumbs Also See for Multilin 350 Series:
Table of Contents

Advertisement

CHAPTER 6: SETPOINTS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
PH TOC CURVE
Range: ANSI Extremely/Very/Moderately/Normally Inverse, Definite Time, IEC Curve A/B/C
and Short Inverse, IAC Extremely/Very/Inverse/Short, User Curve, FlexCurve A, FlexCurve B
Default: Extremely Inverse
This setting sets the shape of the selected TOC inverse curve. If none of the standard
curve shapes is appropriate, a custom User curve, or FlexCurve can be created. Refer to
the User curve and the FlexCurve setup for more detail on their configurations and
usage.
PH TOC TDM
Range: 0.50 to 20.00 in steps of 0.01
Default: 1.00
This setting provides selection for Time Dial Multiplier by which the times from the
inverse curve are modified. For example if an ANSI Extremely Inverse curve is selected
with TDM = 2, and the fault current was 5 times bigger than the PKP level, the operation
of the element will not occur before an elapsed time from pickup, of 495 ms.
PH TOC RESET
Range: Instantaneous, Linear
Default: Instantaneous
The "Instantaneous" reset method is intended for applications with other relays, such as
most static relays, which set the energy capacity directly to zero when the current falls
below the reset threshold. The "Timed" reset method can be used where the relay must
coordinate with electromechanical relays.
OUTPUT RELAY 3 to 6
Range: Do not operate, Operate
Default: Do not operate
Any, or all of the output relays 3 to 6 can be selected to operate, upon phase TOC
operation. The selection of relay outputs operation is available no matter whether
Latched Alarm, Alarm, or Trip function is selected.
BLOCK 1/2/3
Range: Off, Contact Input 1 to 8, Virtual Input 1 to 32, Remote Input 1 to 32, Logic Elements
1 to 8
Default: Off
Three blocking inputs are provided in the Phase TOC menu. When any of the selected
blocking inputs - Contact input, Virtual Input, Remote Input, or Logic Element - turns on,
the phase TOC function will be blocked.
S3 PROTECTION
6–33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents