6.1 Instruction of wired controller

6.1.1 Requirements for model selection of communication wire
Total length of
Wire
communication line
material
between indoor unit
type
and wired controller
L (m/feet)
Light/
Ordinary
Polyvinyl
chloride
L≤250m
sheathed
cord.
(L≤820-1/5feet)
(60227
IEC 52
/60227
IEC 53)
Fig. 6.3 Length of communication wire
Wire size
(mm
/AWG)
2
2×0.75
mm
2
~2×
1.25 mm
2
(2×AWG18
~
2×AWG16)
Wired Controller VEWCL1E
Material
standard
(1)Total length of communication
line can't exceed 250m
(820-1/5feet).
(2)The cord shall be Circular cord
IEC
(the cores shall be twisted
60227-5:20
together).
07
(3)If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
use shielded wire.
11