Control connection 3 - 3 - Wire Start/Stop function.
Enabling the Start/Stop function with 3 Wire control.
Parameters to set:
Set DI3 to START.
P0265 = 6.
Set DI4 to STOP .
P0266 = 7.
Set P0224 = 1 (DIx) for 3 wire control in Local mode.
Set P0227 = 1 (DIx) for 3 wire control in Remote mode.
Set the Forward/Reverse selection by using digital input # 2 (DI2).
Set P0223 = 4 to Local Mode or P0226 = 4 to Remote mode.
S1 and S2 are Start (NO contact) and Stop (NC contact) push-buttons respectively.
The speed reference can be provided through the analog input (as in Control Connection #2), through the
keypad (as in control connection #1) or through any other available source.
Forward/Reverse S3
(FWD/REV)
Start S1
Stop S2
Connector XC1
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND *
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
22
C1
23
NO1
24
NC2
25
C2
26
NO2
27
NC3
28
C3
29
NO3
Figure 3.22 - XC1 wiring for control connection #3
Installation and Connection
DO1
(RL1)
DO2
(RL2)
DO3
(RL3)
3
CFW-11 | 3-33