WEG CFW-11 User Manual page 48

Frequency inverter
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Connector XC1
CW
1
2
≥5 kΩ
3
4
CCW
5
6
7
rpm
8
9
amp
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Factory Default Function
+REF
Positive reference for
potentiometer
AI1+
Analog input #1:
Speed reference (remote)
AI1-
REF-
Negative reference for
potentiometer
AI2+
Analog input #2:
No function
AI2-
AO1
Analog output #1:
Speed
AGND
Reference (0 V) for the analog
(24 V)
outputs
AO2
Analog output #2:
Motor current
AGND
Reference (0 V) for the analog
(24 V )
outputs
DGND * Reference (0 V) for the 24 Vdc
power supply
COM
Common point of the digital
inputs
24 Vdc
24 Vdc power supply
COM
Common point of the digital
inputs
DI1
Digital input #1:
Start / Stop
DI2
Digital input #2:
Direction of rotation (remote)
DI3
Digital input #3:
No function
DI4
Digital input #4:
No function
DI5
Digital input #5:
Jog (remote)
DI6
Digital input #6:
2
ramp
nf
NC1
Digital output #1 DO1 (RL1):
No fault
C1
NO1
NC2
Digital output #2 DO2 (RL2):
N > N
- Speed > P0288
C2
X
NO2
NC3
Digital output #3 DO3 (RL3):
N* > N
- Speed reference >
C3
X
P0288
NO3
(b) Signals at connector XC1 - Digital inputs working as 'Active Low'
Figure 3.17 - (a) and (b) - Signals at connector XC1
Installation and Connection
Specifications
Output voltage:+5.4 V, ±5 %.
Maximum output current: 2 mA
Differential
Resolution: 12 bits
Signal: 0 to 10 V (R
= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
Maximum voltage: ±30 V
Output voltage: -4.7 V, ±5 %.
Maximum output current: 2 mA
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (R
= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
Maximum voltage: ±30 V
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
Protected against short-circuit.
Connected to the ground (frame) through impedance: 940 Ω resistor in
parallel with a 22 nF capacitor.
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
Protected against short-circuit.
Connected to the ground (frame) through impedance: 940 Ω resistor in
parallel with a 22 nF capacitor.
Connected to the ground (frame) through impedance: 940 Ω resistor in
parallel with a 22 nF capacitor.
24 Vdc power supply, ±8 %.
Capacity: 500 mA.
Note: In the models with the 24 Vdc external control power supply (CFW11XXXXXXOW)
the terminal 13 of XC1 becomes an input, i.e., the user must connect a 24 V power
supply for the inverter (refer to the
Item 7.1.3 Nema1 Degree Protection - Frame Sizes
A, B and C on page 7-3
for more details). In all the other models this terminal is an
output, i.e., the user has a 24 V power supply available there.
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @ 24 Vdc
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - Normally closed contact
C - Common
NO - Normally open contact
= 500 Ω)
IN
= 500 Ω)
IN
≤ 500 Ω)
L
3
≤ 500 Ω)
L
CFW-11 | 3-29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents