Parameter
Name
P0100
Acceleration
- Defines the time to linearly accelerate from 0 up to the maximum
Time
speed (P0134)
- If set to 0.0 s, it means no acceleration ramp
P0101
Deceleration
- Defines the time to linearly decelerate from the maximum speed
Time
(P0134) up to 0
- If set to 0.0 s, it means no deceleration ramp
P0133
Minimum
- Defines the minimum and maximum values of the speed reference
Speed
when the drive is enabled
- These values are valid for any reference source
P0134
Maximum
Speed
P0135
Max. Output
- Avoids motor stall under torque overload condition during the
Current
acceleration or deceleration
- The factory default setting is for "Ramp Hold": if the motor
current exceeds the value set at P0135 during the acceleration or
deceleration, the motor speed will not be increased (acceleration)
or decreased (deceleration) anymore. When the motor current
reaches a value below the programmed in P0135, the motor speed
is again increased or decreased
- Other options for the current limitation are available. Refer to the
CFW-11 programming manual
Ramp
acceleration
(P0100)
P0136
Manual Torque
- Operates in low speeds, modifying the output voltage x frequency
Boost
curve to keep the torque constant
- Compensates the voltage drop at the motor stator resistance. This
function operates in low speeds increasing the inverter output voltage to
keep the torque constant in the V/f mode
- The optimal setting is the smallest value of P0136 that allows the
motor to start satisfactorily. An excessive value will considerably increase
the motor current in low speeds, and may result in a fault (F048, F051,
F071, F072, F078 or F183) or alarm (A046, A047, A050 or A110)
condition
Table 5.1 - Parameters comprised in the basic application group
Description
Reference
P0134
P0133
0
0 ................................ 10 V
0 ...............................20 mA
4 mA ............................20 mA
10 V ..................................0
20 mA ...............................0
20 mA ............................4 mA
Motor current
Motor current
P0135
P0135
Time
Speed
Speed
Ramp
deceleration
(P0101)
Time
During
acceleration
Output voltage
Rated
P0136=9
0.5x Rated
P0136=0
0
Nrat/2
First Time Power-Up and Start-Up
Setting Range
0.0 to 999.0 s
0.0 to 999.0 s
0 to 18000 rpm
Alx Signal
0.2 x I
2 x I
Time
Time
During
deceleration
Speed
Nrat
Factory
User
Setting
Setting
20.0 s
20.0 s
90 rpm
(60 Hz motor)
75 rpm
(50 Hz motor)
1800 rpm
(60 Hz motor)
1500 rpm
(50 Hz motor)
to
1.5 x I
rat-HD
rat-HD
rat-HD
0 to 9
1
CFW-11 | 5-7