Table 3.7 - Minimum separation distances between wiring
4. The adequate connection of the cable shield is shown in
page 3-31
shows how to connect the cable shield to the ground.
Inverter
side
Figure 3.20 - Example of shield connection for the control wiring
5. Relays, contactors, solenoids or coils of electromechanical brakes installed close to the inverter may eventually
create interferences in the control circuitry. To eliminate this effect, RC suppressors (with AC power supply)
or free-wheel diodes (with DC power supply) shall be connected in parallel to the coils of these devices.
6. On inverters of frame size D IP2X/Nema1, a shield kit is supplied for better organization of the cables of the
communication network. For further information, refer to the installation data sheet supplied with the kit.
Minimum Separation
Cable Length
Distance
≤ 30 m (100 ft)
≥ 10 cm (3.94 in)
> 30 m (100 ft)
≥ 25 cm (9.84 in)
Figure 3.19 - Shield connection
Installation and Connection
Figure 3.19 on page 3-31
Isolate with tape
Do not ground
and
Figure 3.20 on
3
CFW-11 | 3-31