Electrical connection
6.4.3.

Terminal compartment: close

34
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
Connect all protective earth conductors.
Connect PE connection to external protective earth conductor of connecting
cables.
Start running the device only after having connected the protective earth con-
ductor.
7.
Firmly tighten protective earth to PE connection.
Figure 29: PE connection
[1]
PE connection, control cable
[2]
PE connection, motor cable
Figure 30: Close terminal compartment
[1]
Cover (figure shows KP version)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Flameproof frame
1.
Clean sealing faces of cover [1] and frame [6].
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
SAEx 07.2
SAEx 16.2 / SAREx 07.2
SAREx 16.2